Inputs and Outputs
Occupancy and Generic Binary Input Configuration
Table 6
Table 6. Occupancy and generic binary input configuration
Binary input
type
configuratio
n
Occupancy
Occupancy
Occupancy
Occupancy
Generic
Generic
Generic
Generic
None
Analog Inputs
Each Tracer
no local CO
Table 7. Analog input descriptions and wiring
Analog input
Space temperature
Ground
Space setpoint
Primary air temperature or
Discharge air temperature
Ground
Primary airflow (differential
pressure)
(a) The controller uses a Kavlico differential pressure sensor to calculate the airflow.
12
shows the occupancy and generic binary input configuration.
Binary input
state
configuratio
n
NO
NO
NC
NC
NO
NO
NC
NC
Any state
®
VV550/VV551 controller provides four analog inputs (see
input as there is on the 4.2 VAV controllers.
2
Terminal(s)
Label
TB3-1
ZONE
TB3-2
GND
TB3-3
SET
TB3-5
AUX
TB3-6
GND
J2-3 5VDC
FLOW
J2-2 signal
J2-1 Ground
Contact
Occupancy
mode
Open
Occupied
Closed
Unoccupied
Open
Unoccupied
Closed
Occupied
Open
Occupied
Closed
Occupied
Open
Occupied
Closed
Occupied
Any state
Occupied
Range
Resolution
14°F to 50°F
0.25°F
(–10°C to 10°C)
(0.14°C)
51°F to 95°F
0.125°F
(10.56°C to 35°C)
(0.07°C)
96°F to 122°F
0.25°F
(35.56°C to 50°C)
(0.14°C)
50°F to 90°F
0.5°F
(10°C to 32.2°C)
(0.28°C)
–40°F to 160°F
1°F
(–40°C to 71.11°C)
(0.56°C)
161°F to 212°F
2.5°F
(71.67°C to 100°C)
(1.39°C)
0 to 2 inches water
Less than
1%
(0 to 498 Pascals)
0% to 120%
Generic
Not valid
Not valid
Not valid
Not valid
Inactive
Active
Active
Inactive
Not valid
Table
7). There is
Sensor type
10K at 77°F (25°C)
Thermistor
1K Potentiometer
10K at 77°F (25°C)
Thermistor
Kavlico
differential
®
(a)
pressure sensor
CNT-SVX17G-EN