Parameters
6-72 Terminal 45 Digital Output
Option:
[169] Drive in auto mode
[190] No-Flow
[193] Sleep Mode
3
3
[194] Broken Belt Function
[196] Fire Mode
[198] Drive Bypass
6-73 Terminal 45 Output Min Scale
Range:
0 %
[0 -
*
200 %]
6-74 Terminal 45 Output Max Scale
Range:
100
[0 -
%
200 %]
*
6-76 Terminal 45 Output Bus Control
Range:
0
[0 - 16384 ] Holds the level of analog output if controlled
*
3.7.5 6-9* Analog/Digital Output 42
Parameters for configuring the limits for analog/digital
output terminal 42. Analog outputs are current outputs:
0/4–20 mA. Resolution on analog outputs is 12 bit. Analog
output terminals can also be set up as digital output.
6-90 Terminal 42 Mode
Option:
58
TR150 and TR170
Function:
Function:
Scale for the minimum output (0 mA or 4 mA)
of the analog signal at terminal 45. Set the
value to be the percentage of the full range of
the variable selected in parameter 6-71 Terminal
45 Analog Output.
Function:
Scale for the maximum output (20 mA) of the
analog signal at terminal 45. Set the value to be
the percentage of the full range of the variable
selected in parameter 6-71 Terminal 45 Analog
Output.
Illustration 3.11 Output Maximum Scale
Function:
by bus.
Function:
Set terminal 42 to act as analog output or
as digital output.
6-90 Terminal 42 Mode
Option:
[0]
0-20 mA
*
[1]
4-20 mA
[2]
Digital Output
6-91 Terminal 42 Analog Output
Option:
[0]
No operation
*
[100] Output frequency 0–100 Hz
[101] Reference
[102] Feedback
[103] Motor Current
[106] Power
[139] Bus Control
6-92 Terminal 42 Digital Output
Option:
[0]
No operation
*
[1]
Control Ready
[2]
Drive ready
[3]
Drive ready/remote control
[4]
Standby / no warning
[5]
Drive running
[6]
Running / no warning
[7]
Run in range/no warning
[8]
Run on ref/no warning
[9]
Alarm
[10]
Alarm or warning
[12]
Out of current range
[13]
Below current, low
[14]
Above current, high
[16]
Below speed, low
[17]
Above speed, high
[19]
Below feedback, low
[20]
Above feedback, high
[21]
Thermal warning
[22]
Ready, no thermal warning
[23]
Remote, ready, no thermal
warning
[24]
Ready, Voltage OK
02/2017 All rights reserved.
Function:
Function:
Select the function of terminal 42 as an
analog current output. See also
parameter 6–90 Terminal 42 Mode.
Min
– Max
Ref.
Ref.
Min
– Max
FB
FB
0–I
max
0–P
nom
0–100%
Function:
Select the function of
Terminal 42 as an analog
current output. See also
parameter 6-90 Terminal 42
Mode. See
parameter 5-40 Function
Relay for description of the
choices.
BAS-SVP16B-EN