Trane TR150 Programming Manual page 62

Hide thumbs Also See for TR150:
Table of Contents

Advertisement

Parameters
8-33 Parity / Stop Bits
Option:
Function:
[1] Odd Parity, 1 Stop
Bit
[2] No Parity, 1 Stop
Bit
[3] No Parity, 2 Stop
Bits
8-35 Minimum Response Delay
Range:
Function:
Size
[ 0.0010 - 0.5
Specify the minimum delay time
related
s]
between receiving a request and
*
transmitting a response. This is
used for overcoming modem
turnaround delays.
8-36 Maximum Response Delay
Range:
Function:
Size
[ 0.1 -
Specify the maximum permissible
related
10.0 s]
delay time between receiving a
*
request and transmitting the response.
If this time is exceeded, no response is
returned.
8-37 Maximum Inter-char delay
Range:
Function:
Size related
[ 0.005 -
Specify the maximum delay time
*
0.025 s]
between 2 characters in a message.
Exceeding this delay time causes
the message to be discarded.
3.8.3 8-4* FC MC Protocol Set
This parameter group is for PCD write and read configu-
rations.
8-42 PCD Write Configuration
Different parameters can be assigned to PCD 3–10 of the PPOs
(the number of PCDs depends on the PPO type). The values in
PCD 3–10 are written to the selected parameters as data values.
Option:
[0]
None
[1]
[302] Minimum Reference
[2]
[303] Maximum Reference
[3]
[341] Ramp 1 Ramp up time
[4]
[342] Ramp 1 Ramp down time
[5]
[351] Ramp 2 Ramp up time
[6]
[352] Ramp 2 Ramp down time
[7]
[380] Jog Ramp Time
[8]
[381] Quick Stop Time
[9]
[412] Motor Speed Low Limit
[Hz]
[10]
[414] Motor Speed High Limit
[Hz]
BAS-SVP16B-EN
Programming Guide
8-42 PCD Write Configuration
Different parameters can be assigned to PCD 3–10 of the PPOs
(the number of PCDs depends on the PPO type). The values in
PCD 3–10 are written to the selected parameters as data values.
Option:
[11]
[12]
[13]
[14]
[15]
[16]
8-43 PCD Read Configuration
Different parameters can be assigned to PCD 3–10 of the PPOs
(the number of PCDs depends on the PPO type). PCD 3–10 hold
the actual data value of the selected parameters.
Option:
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]
[14]
[15]
[16]
[17]
[18]
[19]
[20]
Function:
[21]
[22]
[23]
[24]
[25]
[26]
[27]
[28]
[29]
[30]
[31]
[32]
[33]
02/2017 All rights reserved.
[590] Digital & Relay Bus
Control
[676] Terminal45 Output Bus
Control
[696] Terminal 42 Output Bus
Control
[894] Bus Feedback 1
FC Port CTW
FC Port REF
None
[1500] Operation Hours
[1501] Running Hours
[1502] kWh Counter
[1600] Control Word
[1601] Reference [Unit]
[1602] Reference %
[1603] Status Word
[1605] Main Actual Value [%]
[1609] Custom Readout
[1610] Power [kW]
[1611] Power [hp]
[1612] Motor Voltage
[1613] Frequency
[1614] Motor Current
[1615] Frequency [%]
[1618] Motor Thermal
[1630] DC Link Voltage
[1634] Heatsink Temp.
[1635] Inverter Thermal
[1638] SL Controller State
[1650] External Reference
[1652] Feedback [Unit]
[1660] Digital Input 18,19,27,33
[1661] Terminal 53 Switch Setting
[1662] Analog Input 53(V)
[1663] Terminal 54 Switch Setting
[1664] Analog Input 54
[1665] Analog Output 42 [mA]
[1671] Relay Output [bin]
[1672] Counter A
[1673] Counter B
[1690] Alarm Word
[1692] Warning Word
Function: