Compatibility With The Fp3 - Panasonic FP2 ET-LAN Technical Manual

Table of Contents

Advertisement

Compatibility with the FP3

Differences with the FP3 ET-LAN unit
The main differences between the specifications and operation of the FP2 ET-LAN unit and the FP3 ET-
LAN unit are given in the table below. Refer to the reference page numbers given for each item for
details regarding specifications and operation.
Item
Communication
interface
100BASE-TX, 10BASE-T, and 10BASE5
(See page 1-4.)
1. 100BASE-TX/10BASE-T and 10BASE5 switch
Mode setting
2. Reserved
switch
3. Normal mode/test mode switch
(See page 2-3.)
4. Test mode operation selection
Mounting
The following quantities can be inserted in any of
position/qty.
the master backplane slots (including Multi-wiring
limits
link unit MEWNET-W2 mode)
(See page 1-11
With the FP2 CPU unit: 3 units
and 1-12.)
With the FP2SH CPU unit: 8 units
Handshaking
I/O handshaking and shared-memory handshaking
(See page 4-8.)
can be used simultaneously.
I/O handshaking signals
Deleted: I/O handshake mode flag (XE)
Handshake
Shared memory handshake signal
signals
Deleted: I/O handshake mode flag
(See pages 4-9
(bank 0: 360H bit E)
to 4-12.)
Added: Expansion complete signal area 2
(bank 0: 366H)
Connection data notification block
(bank 0: 2E0H to 35FH)
Added: Receive processing complete code
Shared memory
(See page 15-5.)
Test items
1. Mode setting switch test
2. LED test
3. ROM test
4. RAM test
Test mode
5. Shared memory test
(See page 3-6.)
6. Timer test
7. Internal loopback test
8. External loopback test
Added: Mode setting switch test
Deleted: EEPROM checksum test
Modified: LED display during testing and error
Error codes added
8036H: MEWTOCOL transmission error
Error codes deleted
Error log
8006H: OFFLINE error
(See page 12-7.)
8009H: Mode change error
8019H: Forced close error
B001H/B002H: ONLINE/OFFLINE switching error
Ladder programs created using the FP3 can be
Ladder program
used without modification.
FP2 ET-LAN unit
(offset address A)
Receive unnotified data size
(offset address B)
Receive unnotified data size copy
(offset address C)
during operation
FP3 ET-LAN unit
10BASE5
1. Test mode operation selection
2. Handshake mode selection
3. ONLINE/OFFLINE switch
4. Normal mode/test mode switch
The following quantities can be inserted
in any of the master backplane slots
(including MEWNET-H link unit)
FP3/FP10SH CPU unit: 3 units
The mode setting switch is used to switch
between I/O handshaking and shared
memory handshaking.
-
-
Test items
1. LED test
2. ROM test
3. RAM test
4. Shared memory test
5. EEPROM checksum test
6. Timer test
7. Internal loopback test
8. External loopback test
-
-
vii

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fp2-et1Fp2-et2Afp27901Afp2790

Table of Contents