Panasonic FP2 ET-LAN Technical Manual page 208

Table of Contents

Advertisement

Code
Name
8010H
Open error
8011H
Application use
error
8012H
Source node
port No. error
8013H
Partner node
port No. error
8014H
Partner node IP
address error
8015H
UDP/IP source
node port
number
duplication error
8016H
TCP/IP source
node port
number
duplication error
8017H
Memory error
8018H
No partner node
error
801AH
Forced close
error
801BH
Destination
MEWTOCOL
station number
setting error
12-8
Description
An attempt was made to
execute open processing
although initialization
processing was not completed
successfully.
A setting other than Active,
Fullpassive or Unpassive was
entered when using TCP/IP (not
applicable if UDP/IP is being
used).
0 was set for the source node
port number during open
processing.
0 was set for the partner node
port number in a mode other
than TCP/IP Unpassive, during
open processing.
During open processing:
With UDP/IP, 0 was set for the
partner node IP address.
0H or FFFFFFFFH was set for
the partner node IP address in
a mode other than TCP/IP
Unpassive.
The same source node port
number was set in UDP/IP as
that of a source node port that
is already open.
The same source node port
number was set in TCP/IP as
that of a source node port that
is already open.
The connection cannot be
opened because not enough
memory is available.
The connection cannot be
opened because the
transmission destination of the
specified partner node IP
address and port number
cannot be found, or a
communication error occurred.
The connection was forcibly
closed because the initialization
request signal went off.
A value other than 1 to 64 was
set for the MEWTOCOL station
number of the partner node.
Step to take
Run the open processing
after the initialization
processing has been
completed.
Correct the setting area for
the application being used.
Correct the source node
port number
Correct the partner node
port number.
Correct the IP address of
the partner node.
Specify a different source
node port number.
Specify a different source
node port number.
Run the open processing
again. If the error still
occurs, run the
initialization processing
once again.
Check the transmission
line connection, the IP
address of the partner
node, and the port number
of the partner node.
Turn the initialization
request complete signal off
after close processing has
been completed.
Correct the MEWTOCOL
station number of the
partner node.
Remark
Open
processing
end code
There are also
stored in offset
address 0 of the
open processing
end code of the
connection
information notified
area.
Open
processing
end code
There are also
stored in offset
address 0 of the
open processing
end code of the
connection
information notified
area.