Specifications; General - Polaris DP-20 User Manual

Web guide controller
Hide thumbs Also See for DP-20:
Table of Contents

Advertisement

General

Universal Input Line
Voltage Range
Input Line Frequency
Power consumption
Internal Fuse
Operating Ambient
Temperature
Dimensions
Approximate Weight
Inputs and Outputs
Electromechanical Actuator
Hydraulic Servo Valve
MPA (with MPA Lockout Signal) - ±10 mA
ServoCenter
Sensor Input (2) Individually
Programmable
Parallel port
Supply to Accessories
06-05-2007
DP-20 WEB GUIDE CONTROLLER USER MANUAL
- 100 VAC -10% to
240 VAC +10%
- 47-63 Hz
- 130 VA
- 3.15 A (not user serviceable)
- 0° to 50°C (32° to 122°F)
- Height 144 mm (5.67")
Width 144 mm (5.67")
Depth 103 mm (4.06") (without cables attached)
- 1.6 Kg (3.5 lbs)
- Maximum 39 W at 30 V
- ±50 mA
With or without Lockout Valve (Max 39 W at 24 V or 48 V)
- Analog Inductive type
- Max Input ±20 mA
0 to 10 mA (Preferred)
- Six Digital Inputs
Low Level: 0 – 0.9 V
High level: 3.6 – 24 V, max 6 mA
Two open collector outputs connected to ground, max 30 V
(NPN open collector) 55 mA at 1.6 V
+12 V available to port for input reference
- +12V±5%, 400mA
-12V±5%, 150mA
DP-20 WEB GUIDE CONTROLLER
10

SPECIFICATIONS

Figure Sheet 1-862-D
10
10-1