7.4 Input #1, #2, or #3 Set Up Wiring
Thermocouple inputs
using an ice bath
4/00
Referring to Figure 7-2, wire the controller according to the procedure
given in Table 7-3.
Table 7-3
Set Up Wiring Procedure for Thermocouple Inputs Using an
Step
1
Connect the copper leads to the calibrator.
2
Connect a length of thermocouple extension wire to the end of each copper
lead and insert the junction points into the ice bath.
3
Connect the thermocouple extension wires to the terminals for Input #1 or
Input #2. See Figure 7-2.
4
Connect a cold junction resistor to terminals 25 and 27 for Input #1 or
terminals 22 and 24 for Input #2. See Figure 7-2.
Figure 7-2
Wiring Connections for Thermocouple Inputs
Input 2
Input 1
T/C Extension Wire
UDC 3300 Process Controller Product Manual
Ice Bath
Action
Using an Ice Bath