Alarm Setpoints; Table 5-20 Procedure For Displaying Or Changing The Alarm Setpoints - Honeywell UDC 3300 Product Manual

Universal digital controller
Hide thumbs Also See for UDC 3300:
Table of Contents

Advertisement

5.11 Alarm Setpoints

Introduction
Procedure for
displaying the alarm
setpoints
4/00
An alarm consists of a relay contact and an operator interface indication.
The alarm relay is de-energized if setpoint 1 or setpoint 2 is exceeded.
The alarm relay is energized when the monitored value goes into the
allowed region by more than the hysteresis.
The relay contacts can be wired for normally open (NO) energized or
normally closed (NC) de-energized at the rear terminals. See Table 2-8 in
the Section 2 – Installation for alarm relay contact information.
There are four alarm setpoints, two for each alarm. The type and state
(High or Low) is selected during configuration. See Section 3 –
Configuration for details.
Table 5-20 lists the procedure for displaying and changing the alarm
setpoints.
Table 5-20
Procedure for Displaying or Changing the Alarm Setpoints
Step
Operation
1
Access the
Alarm Set Up
group
2
Access the
Alarm Setpoint
Values
3
Return to normal
operation
UDC 3300 Controller Product Manual
Press
until you see:
SET UP
Upper Display
SET UP
Lower Display
ALARMS
to successively display the alarm setpoints
FUNCTION
and their values. Their order of appearance
LOOP 1/2
is shown below.
Upper Display
Lower Display
A1S1 VAL =
A1S2 VAL =
A2S1 VAL =
A2S2 VAL =
to change any alarm setpoint value you
or
select in the upper display.
LOWER
DISPLAY
Action
The alarm setpoint
value
(Alarm 1, Setpoint 1 value)
(Alarm 1, Setpoint 2 value)
(Alarm 2, Setpoint 1 value)
(Alarm 2, Setpoint 2 value)
171