3.8

SP Ramp, SP Rate, or SP Programming Set Up Group

Single Setpoint Ramp
Setpoint rate
Function prompts
Function Prompt
Lower Display
SP RAMP
Single Setpoint Ramp
Selection
TIME MIN
Single Setpoint Ramp Time
(SP ramp enabled)
FINAL SP
Single Setpoint Final
Setpoint (SP ramp enabled)
SP RATE
Setpoint Rate
EU/HR UP
Rate Up Value for
Loop 1 (SP Rate enabled)
EU/HR DN
Rate Down Value for
Loop 1 (SP Rate enabled)
EU/HRUP2
Rate Up Value for
Loop 2 (SP Rate enabled)
EU/HRDN2
Rate Down Value for
Loop 2 (SP Rate enabled)
SP PROG*
Setpoint Ramp/Soak
Programming
STRT SEG
Start Segment Number
END SEG
End Segment Number
RAMPUNIT
Engineering Units for Ramp
Segments
4/00
The Setpoint Ramp Set Up group contains the Function parameters that let
you configure a single setpoint ramp to occur between the current local
setpoint and a final setpoint over a time interval (SP RAMP).
The Setpoint Ramp Set Up group also contains the function parameters
that let you configure a specific rate of change for any Local Setpoint
change (SP RATE). It includes selections for Rate Up and Rate Down.
Table 3-5 lists all the function prompts in the SP Ramp Set Up group.
Table 3-5
SP Ramp Group Function Prompts
Function
Name
If SP Rate and SP Programming are disabled
DISABL
ENABLE
ENABL2
ENAB12
0 to 255 minutes
Enter a value within the setpoint limits.
If SP Ramp and SP Programming are disabled
DISABL
ENABLE
ENABL2
ENAB12
0 to 9999
in engineering units per hour
0 to 9999
in engineering units per hour
0 to 9999
in Units per Hour
0 to 9999
in Units per Hour
If SP Ramp and SP Rate are disabled
DISABL
ENABLE
ENABL2
ENAB12
SP PROG must be enabled to view
the remaining prompts.
1 to 11
2 to 12
Always end in a soak segment
(2, 4, ... 12)
TIME
EU/MIN (engineering units/minute)
EU/HR
UDC 3300 Process Controller Product Manual
Selections or
Range of Setting
Upper Display
(hours.minutes)
(engineering units/hour)
Factory
Refer
Setting
to
DISABL
Section
4.4
3
1000
DISABL
0
0
0
0
DISABL
––
––
TIME
45