6.4 Entering the Setpoint Program Data

Introduction
Table 6-1
Step
Action
1
Select SP PROG
Group
2
Select the functions
3
Change the value or
selection of a function
prompt
4
Enter value or
selection into memory
5
Exit configuration
Alarms on the setpoint
program
Prompt hierarchy
4/00
The procedure listed in Table 6-1 tells you what keys to press and what
prompts you will see when entering the setpoint program data. Follow the
prompt hierarchy listed in Table 6-2 when selecting the functions for
setpoint programming.
ATTENTION
Make sure SP RAMP and SP RATE are disabled first.
Setpoint Program Data Entry Procedure
Press
until you see
SET UP
Upper Display
Lower Display
to enable the setpoint programming option on Loop 1, Loop 2,
or
or both.
This accesses the function prompts SP Programming.
FUNCTION
LOOP 1/2
Upper Display
Lower Display
Successive presses of the [FUNCTION] key will sequentially
display all the functions and their values or selections. Follow
the prompt hierarchy shown in Table 6-2.
This changes the value or selection in the upper display. If the
or
display blinks, you are trying to select an unacceptable value.
This enters the value or selection and goes to another prompt.
FUNCTION
Repeat steps 3 and 4 for each function you want to change.
LOOP 1/2
This exits from the configuration mode.
LOWER
DISPLAY
You can configure an event to go ON or OFF at the beginning or end of
any segment. Refer to Section 3 - Configuration under "Alarms
Parameters Group" for details.
Table 6-2 lists all the function prompts for Setpoint Program data
configuration in the order of their appearance. Follow the procedure in
Table 6-1 to transfer the data from your setpoint Ramp/Soak profile into
the controller. All parameters may be changed while the program is
disabled or in HOLD.
UDC 3300 Controller Product Manual
Result
ENABLE
ENABL2
ENAB12
SP PROG
Shows the current value for each
prompt.
The individual function prompts within
the setpoint program group are shown.
211

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents