Input 1 Set Up Wiring - Honeywell UDC2300 Product Manual

Universal digital controller
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

8.4 Input 1 Set Up Wiring

Thermocouple Inputs Using an Ice Bath
Refer to Figure 8-2 and wire the controller according to the procedure given in Table 8-3.
Make sure the jumper at S101 is in the #1 position. See Figure 2-2 Jumper Placements.
Table 8-3 Set Up Wiring Procedure for Thermocouple Inputs
Step
Connect the copper leads to the calibrator.
1
Connect a length of thermocouple extension wire to the end of each copper lead and
2
insert the junction points into the ice bath.
3
Connect the thermocouple extension wires to the terminals for Input #1.
See Figure 8-2.
Millivolt
Source
Copper Leads
Figure 8-2 Wiring Connections for Thermocouple Inputs Using an Ice Bath
Thermocouple Inputs Using a Thermocouple Source
Refer to Figure 8-3 and wire the controller according to the procedure given in Table 8-4.
Make sure the jumper at S101 is in the #1 position. See Figure 2-2 Jumper Placements.
Table 8-4 Set Up Wiring Procedure for Thermocouple Inputs using
Step
Connect the thermocouple extension wires to the terminals for Input #1 as shown in
1
Figure 8-3.
Figure 8-3 Wiring Connections for Thermocouple Inputs Using
12/00
Using an Ice Bath
+
_
Thermocouple Source
+
Thermocouple
_
Source
Thermocouple
Extension Wire
Thermocouple Source
UDC2300 Controller Product Manual
Action
Ice Bath
Action
Input Calibration
+
8
_
7
24872
Thermocouple
Extension Wire
8
+
_
7
24873
87