Table 5-39 Accutune* Error Prompt Definitions - Honeywell UDC 3300 Product Manual

Universal digital controller
Hide thumbs Also See for UDC 3300:
Table of Contents

Advertisement

Error prompt
Upper Display
Prompt
NONE
OUTLIM
IDFAIL
ABORT
(Only error code
available for TUNE)
LOW PV
RUNING
*Does not apply to PV Adapt.
4/00
Table 5-39 lists the Accutune error prompts and their definitions.
Table 5-39
Accutune* Error Prompt Definitions
Prompt Definition
No errors
SP Adapt step is greater than high output
limit or less than low output limit
Output step insufficient to get to SP value
Process Identification Failure
An illegal value of gain, rate, or reset was
calculated.
• Manual abort has occurred
– Accutune will abort if the
MANUAL/AUTO key is pressed
during tuning
• Digital input detected
• Automatic abort has occurred
– Accutune will automatically abort when
a PV oscillation has been detected
during SP adapt, whenever any SP
values are changed during a PV adapt
tune, or when Accutune is disabled.
PV not changed sufficiently or the PV has
increased by more than 4 % and dead
time not determined.
Informational prompt indicating that SP
tune is still active checking process gain
even though T is not lit. It does not affect
the keyboard operation.
UDC 3300 Controller Product Manual
Action to Take
None
• Check the output limits under Control Set
Up group function prompts OUTHiLIM and
OUTLoLIM in Section 3 – Configuration.
• Verify the Process Gain Value, function
prompt KPG or KPG 2.
Try to SP tune again. Insure the process is at
line-out prior to initiation of SP tune.
Try to TUNE or SP tune again.
NONE—After a period of about five minutes,
the SP adaptive tuning will be retried
automatically with a larger output step.
NONE