6.5 Run/Monitor the Program

Introduction
Run/monitor functions
214
Make sure all the "SP PROG" function prompts under the Set Up group
"SP RAMP" have been configured with the required data.
An "H" will appear in the upper display indicating that the program is in
the HOLD state.
Table 6-3 lists all the functions required to run and monitor the program.
Table 6-3
Function
Set the Local
Setpoint
Run State
Hold State
External Hold
DI = "To Hold"
Changing a Segment
while in Hold
UDC 3300 Controller Product Manual
Run/Monitor Functions
Press
You will see
SETPOINT
Upper Display
SELECT
Lower Display
SP
to set the Local Setpoint value to where you
or
want the program to start out.
Initiates the setpoint program.
RUN
HOLD
An "R" appears in the upper display
indicating that the program is running.
Holds the setpoint program. An "H" appears
RUN
in the upper display indicating that the
HOLD
program is in the HOLD state.
The setpoint holds at the current setpoint.
If Remote Switching (Digital Input option) is
present on your controller, contact closure
places the controller in the HOLD state, if the
setpoint program is running. The "H" in the
upper display will blink indicating external
hold is in effect.
ATTENTION
priority over external switch for the
RUN/HOLD function.
Contact reopening runs program.
These keys will operate and allow you to
or
change the segment number while in HOLD.
If a different segment is selected, it will be
started at the beginning when placed in
RUN. If the original segment is brought back,
the program will continue from the point
placed in HOLD.
NOTE: Changing a segment number may
affect the alarms/events.
Result
Local Setpoint Value
The keyboard takes
4/00