Table 6-2
Prompt Hierarchy and Available Selections
Prompt
Definition
(Lower
Display)
SP RAMP
Setpoint Ramp Selection
SP RATE
Setpoint Rate of Change
SP PROG
Setpoint Ramp/Soak
Programmer
STRT SEG
Start Segment Number
END SEG
End Segment Number
RAMPUNIT
Engineering Units from
Ramp Segments
RECYCLES
Number of Program
Recycles
SOAK DEV
Guaranteed Soak Deviation
Value
PROG END
Program Termination State
STATE
Program State at Program
End
KEYRESET
Reset/rerun SP Program
PV Hot Start
HOTSTART
Program Initialization or
power up in SPP
SEG1RAMP
Segment #1 Ramp Time
or
or
SEG1RATE
Segment #1 Ramp Rate
UDC 3300 Controller Product Manual
Value or Selection (use
(Upper Display)
Selections:
DISABL
SP RAMP must be disabled to allow
Setpoint Programming.
Selections:
DISABL
SP RATE must be disabled to allow
Setpoint Programming.
Selections:
DISABL
ENABLE—Loop 1
ENABL2—Loop 2
ENAB12—Loops 1 and 2
SP PROG must be enabled to view
the remaining prompts.
Enter Value:
1 to 11
Enter Value:
2 to 12
Always end in a soak Segment
(2,4,.....12)
Selections:
TIME
EU/MIN
EU/HR
Enter Value:
0 to 99 recycles
Enter Value:
0 to +99.00
The number selected will be
0 to 99 ± from setpoint.
Selections:
LASTSP—Hold at
last setpoint in the
program
F SAFE—Manual
mode/Failsafe
output
Selections:
DISABL
HOLD (hold mode)
Selections:
DISABL
RERUN
TOBEGN
Selections:
DISABL—LSP1 is
used as the initial
ramp setpoint.
ENABL—PV value is
used as the initial
ramp setpoint.
Enter Value:
Ramp Time = 0-99hr.0-59min, or
Ramp Rate = Engineering units/min
or Engineering units/hr
Select TIME, EU/MIN, or EU/HR at
prompt "RAMP UNIT". All ramps will
use the same selection.