Monitoring Two Loops Of Control; Table 5-28 Digital Display Indication-Two Loops - Honeywell UDC 3300 Product Manual

Universal digital controller
Hide thumbs Also See for UDC 3300:
Table of Contents

Advertisement

5.14 Monitoring Two Loops of Control

Introduction
Loop display
Viewing each loop's
process variable
Internal cascade
indication
180
Monitoring two individual loops of control or internal Cascade is the same
as a single loop except as indicated in Table 5-28.
Table 5-28
Indicator
Loop Indication
none
Loop 1
(two-loop)
I
(cascade)
L"
Loop 2
Display of Loop 1 or Loop 2 (if configured) is selected by toggling the
FUNCTION / LOOP 1/2 key.
Regardless of which loop is being displayed, 1 or 2, the process variable
of the non-displayed loop can be shown in the lower display by repeated
presses of the LOWER DISPLAY key until 1PVXXXX or 2PVXXXX
is displayed.
When internal Cascade has been configured, an "I" will appear on the left
side of the upper display as long as Loop 1 is operating in the remote
setpoint mode. Hold in the SETPOINT SELECT key until RSP appears
in the lower display then release the key to select remote setpoint.
Switching between automatic and manual mode on either loop will not
affect the internal Cascade indication.
UDC 3300 Controller Product Manual
Digital Display Indication—Two Loops
• Upper display shows the Process Variable
(PV) for Loop 1
• Lower display shows the Loop 1
parameters and the PV and Output for
Loop 2
• Controller setpoint annunciators show the
setpoint currently being used for Loop 1
• Upper display shows the Process Variable
(PV) for Loop 2
• Lower display shows the Loop 2
parameters and the PV and Output for
Loop 1
• Controller setpoint annunciators show the
setpoint currently being used for Loop 2
Definition
4/00

Hide quick links: