Honeywell UDC 3300 Product Manual page 73

Universal digital controller
Hide thumbs Also See for UDC 3300:
Table of Contents

Advertisement

Function Prompt
Lower Display
OUT RATE
Output Change Rate
PCT/M UP
Output Rate Up Value
PCT/M DN
Output Rate Down Value
OUTHiLIM
High Output Limit
OUTLoLIM
Low Output Limit
I HiLIM
High Reset Limit
I LoLIM
Low Reset Limit
DROPOFF
Controller Dropoff Value
DEADBAND
Output Relay Deadband
FAILMODE
Failsafe Mode
FAILSAFE
Failsafe Output Value
4/00
Function
Name
ENABLE
DISABL
0 to 9999 % per minute
0 to 9999 % per minute
–5 to 105 % of output
–5 to 105 % of output
Within the range of the output limits
Within the range of the output limits
–5 to 105 % of output
–5.0 to 5.0 %
NO LAT
LATCH
Set within the range of the output
limits. 0 to 100 %
UDC 3300 Process Controller Product Manual
Selections or
Range of Setting
Upper Display
Factory
Refer
Setting
to
Section
DISABL
4.12
0
0
100
0
100.0
0.0
0
1.0
NO LAT
0
61