Lower Display
Prompt
LANGUAGE
4.17 Calibration Data
Introduction
4.18 Maintenance Group
Introduction
Maintenace group
prompts
Lower Display
Prompt
TIME1
144
Upper Display
Range of Setting
or Selection
ENGLIS
FRENCH
GERMAN
SPANIS
ITALAN
The prompts used here are for field calibration purposes. Refer to Section
6 – Input Calibration in this manual for complete information.
The Maintenance group prompts are part of the HealthWatch feature.
These prompts let you count and time the activity of discrete events such
as relays, alarms, control modes and others, to keep track of maintenance
needs.
Table 4-16 lists all the function prompts in the Maintenance Set Up group.
Table 4-16
Maintenance Group Definitions
Upper Display
Range of Setting
or Selection
DISABL
LASTR
AL1SP1
AL1SP2
AL2SP1
AL2SP2
MANUAL
UDC 3300 Process Controller Product Manual
Parameter
Definition
LANGUAGE—This selection designates the prompt
language.
ENGLISH
FRENCH
GERMAN
SPANISH
ITALIAN
Parameter
Definition
TIMER 1—The timer tracks the elapsed time of the
selected event.
DISABL—Disables the timer.
LAST RESET—Time elapsed since the last reset.
ALARM 1 SETPOINT 1—Cumulative time Alarm 1
Setpoint 1 was activated.
ALARM 1 SETPOINT 2— Cumulative time Alarm 1
Setpoint 2 was activated.
ALARM 2 SETPOINT 1— Cumulative time Alarm 2
Setpoint 1 was activated.
ALARM 2 SETPOINT 2— Cumulative time Alarm 2
Setpoint 2 was activated.
LOOP 1 MANUAL—Cumulative time Loop 1 was in
Manual.
4/00