Table 5-8 Changing Operating Modes - Honeywell UDC 3300 Product Manual

Universal digital controller
Hide thumbs Also See for UDC 3300:
Table of Contents

Advertisement

What happens when
you change modes
4/00
Table 5-8 explains what happens to the controller when you switch from
one mode to another.
Table 5-8
Mode Change
Manual to Automatic
Local Setpoint
Manual or Auto Local to
Automatic Remote SP
Automatic Remote
Setpoint to Manual or
Auto Local Setpoint
UDC 3300 Controller Product Manual
Changing Operating Modes
Description
The Local Setpoint is usually the value previously stored as
the Local Setpoint.
PV tracking is a configurable feature which modifies this.
For this configuration, when a loop is in manual mode, the
local setpoint value tracks the process variable value
continuously.
The Remote Setpoint uses the stored ratio and bias to
calculate the control setpoint.
Auto bias is a configurable feature which modifies this.
When it is selected the transfer from automatic local to
automatic remote or from manual remote to automatic
remote adjusts the bias based on the local setpoint such
that Bias = LSP – (RSP Input x R).
If configured for Local Setpoint Tracking, when the
controller transfers out of remote setpoint the last value of
the control setpoint is inserted into the local setpoint.
If LSP tracking is not configured, the local setpoint will not
be altered when the transfer is made.
157