Advertisement

Input Calibration
Type of Input

5.4 Input 1 Set Up Wiring

Thermocouple Inputs Using an Ice Bath
Refer to Figure 5-2 and wire the controller according to the procedure given in Table
5-3..
Table 5-3 Set Up Wiring Procedure for Thermocouple Inputs
Step
Connect the copper leads to the calibrator.
1
Connect a length of thermocouple extension wire to the end of each copper lead and
2
insert the junction points into the ice bath.
3
Connect the thermocouple extension wires to the terminals for Input #1.
See Figure 5-2.
Millivolt
Source
Copper Leads

Figure 5-2 Wiring Connections for Thermocouple Inputs Using an Ice Bath

Do not switch current sources OFF/ON while connected to the
UDC2500 input.
Using an Ice Bath
+
_
UDC2500 Universal Digital Limit ControllerProduct Manual
Equipment Needed
Action
Ice Bath
+
26
_
27
Thermocouple
Extension Wire
62