Step
Description
4
DO AUTO
Set 0 % value
5
DO AUTO
Set 100 % value
6
DO MAN
Set 0 % value
7
DO MAN
Set 100 % value
238
Press
to select automatic or manual calibration.
or
Upper Display
Lower Display
POS PROP
ATTENTION
selection reverts to DISABL.
The decrement relay is turned on to move the motor to
FUNCTION
0 % position.
LOOP 1/2
Upper Display
Lower Display
ZERO VAL
When the motor stops, the display should stop counting,
then go to the next step.
The increment relay is turned on to move the motor to
FUNCTION
100 % position.
LOOP 1/2
Upper Display
Lower Display
SPAN VAL
When the motor stops, the display should stop counting,
then, go to Step 8.
You will see:
FUNCTION
Upper Display
LOOP 1/2
Lower Display
ZERO VAL
until the desired zero value is reached in the upper
or
display.
Upper Display
Lower Display
ZERO VAL
The controller will store the 0 % value and you will see:
FUNCTION
Upper Display
LOOP 1/2
Lower Display
SPAN VAL
UDC 3300 Controller Product Manual
Action
DO AUTO
or
DO MAN
If you select...
Then...
DO AUTO
go to Step 4
DO MAN
go to Step 6
When calibration is terminated, this
counts of feedback
slidewire (0 to 3000)
counts of feedback
slidewire (0 to 3000)
The existing zero
calibration value
in counts.
The desired zero
value
The existing span
calibration value
in counts
4/00