Differential protection
Table of Contents

Advertisement

Feeder 5
Address 601 STRPNT->BUS I5 = transformer starpoint versus busbar for feeder 5,
Address 602 IN-PRI CT I5 = rated primary transformer current for feeder 5,
Address 603 IN-SEC CT I5 = rated secondary transformer current for feeder 5.
Feeder 6
Address 611 STRPNT->BUS I6 = transformer starpoint versus busbar for feeder 6,
Address 612 IN-PRI CT I6 = rated primary transformer current for feeder 6,
Address 613 IN-SEC CT I6 = rated secondary transformer current for feeder 6.
Feeder 7
Address 621 STRPNT->BUS I7 = transformer starpoint versus busbar for feeder 7,
Address 622 IN-PRI CT I7 = rated primary transformer current for feeder 7,
Address 623 IN-SEC CT I7 = rated secondary transformer current for feeder 7.
The following settings are only available in 7UT613/63x:
Feeder 8
Address 631 STRPNT->BUS I8 = transformer starpoint versus busbar for feeder 8,
Address 632 IN-PRI CT I8 = rated primary transformer current for feeder 8,
Address 633 IN-SEC CT I8 = rated secondary transformer current for feeder 8.
Feeder 9
Address 641 STRPNT->BUS I9 = transformer starpoint versus busbar for feeder 9,
Address 642 IN-PRI CT I9 = rated primary transformer current for feeder 9,
Address 643 IN-SEC CT I9 = rated secondary transformer current for feeder 9.
The following settings are only available in 7UT635:
Feeder 10
Address 651 STRPNT->BUS I10 = transformer starpoint versus busbar for feeder 10,
Address 652 IN-PRI CT I10 = rated primary transformer current for feeder10,
Address 653 IN-SEC CT I10 = rated secondary transformer current for feeder 10.
Feeder 11
Address 661 STRPNT->BUS I11 = transformer starpoint versus busbar for feeder 11,
Address 662 IN-PRI CT I11 = rated primary transformer current for feeder 11,
Address 663 IN-SEC CT I11 = rated secondary transformer current for feeder 11.
Feeder 12
Address 671 STRPNT->BUS I12 = transformer starpoint versus busbar for feeder 12,
Address 672 IN-PRI CT I12 = rated primary transformer current for feeder 12,
Address 673 IN-SEC CT I12 = rated secondary transformer current for feeder 12.
Current Transformer Data for 1-phase Further Current Inputs
The number of 1-phase further current inputs depends on the device version. Such inputs are used for detec-
tion of the starpoint current of an earthed winding of a transformer, generator, or motor, shunt reactor, or
neutral reactor, or for different 1-phase measuring purposes. The assignment has already been carried out in
Section
2.1.4 Power System Data
the assignment of the protection functions will be done in Section "Assignment of the Protection Functions to
the Measuring Locations/Sides". These settings concern exclusively the current transformer data, regardless of
whether or not they belong to the main protected object.
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
1, margin heading "Assignment of Auxiliary 1-phase Measuring Locations",
Functions
2.1 General
65