Siemens SIPROTEC 4 7UT6 Series Manual page 330

Differential protection
Table of Contents

Advertisement

Mounting and Commissioning
3.1 Mounting and Connections
[ein-ausgabebgr-c-io-2-ab-ausgabe7-251103-oz, 1, en_GB]
Figure 3-11
The relay contacts of the binary outputs BO6 to BO8 can be changed from NO (normally open) to NC (normally
closed) operation (refer also to Appendix
Table 3-15
for
BO6
BO7
BO8
1)
Delivery state
330
C-I/O-2 input/output board release 7UT6x .../EE or higher, with representation of jumper
settings required for checking configuration settings
B Terminal
Jumper setting for the Contact Type of the relay for BO6 to BO8
Jumper
Quiescent state open (close)
X41
1-2
X42
1-2
X43
1-2
Assignments).
Quiescent state closed (open)
1)
2-3
2-3
2-3
C53000-G1176-C230-5, Edition 09.2016
SIPROTEC 4, 7UT6x, Manual