Siemens SIPROTEC 4 7UT6 Series Manual page 579

Differential protection
Table of Contents

Advertisement

Addr. Parameter
5316
T U>>
5317A DOUT RATIO
5318A VALUES
5601
O/U FREQUENCY
5611
f<
5612
f<<
5613
f<<<
5614
f>
5621
f<
5622
f<<
5623
f<<<
5624
f>
5631
f<
5632
f<<
5633
f<<<
5634
f>
5641
T f<
5642
T f<<
5643
T f<<<
5644
T f>
5651
Umin
5652
U MIN
7001
BREAKER FAILURE
7011
START WITH REL.
7012
START WITH REL.
7015
T1
7016
T2
7101
BREAKER FAILURE
7111
START WITH REL.
7112
START WITH REL.
7115
T1
7116
T2
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
Function
C
Setting Options
Overvoltage
0.00 .. 60.00 sec; ∞ 0.50 sec
Overvoltage
0.90 .. 0.99
Overvoltage
U-ph-ph
U-ph-e
Frequency Prot.
OFF
ON
Block relay
Frequency Prot.
40.00 .. 49.99 Hz; 0 49.50 Hz
Frequency Prot.
40.00 .. 49.99 Hz; 0 48.00 Hz
Frequency Prot.
40.00 .. 49.99 Hz; 0 47.00 Hz
Frequency Prot.
50.01 .. 66.00 Hz; ∞ 52.00 Hz
Frequency Prot.
50.00 .. 59.99 Hz; 0 59.50 Hz
Frequency Prot.
50.00 .. 59.99 Hz; 0 58.00 Hz
Frequency Prot.
50.00 .. 59.99 Hz; 0 57.00 Hz
Frequency Prot.
60.01 .. 66.00 Hz; ∞ 62.00 Hz
Frequency Prot.
10.00 .. 16.69 Hz; 0 16.50 Hz
Frequency Prot.
10.00 .. 16.69 Hz; 0 16.00 Hz
Frequency Prot.
10.00 .. 16.69 Hz; 0 15.70 Hz
Frequency Prot.
16.67 .. 22.00 Hz; ∞ 17.40 Hz
Frequency Prot.
0.00 .. 100.00 sec;
Frequency Prot.
0.00 .. 600.00 sec;
Frequency Prot.
0.00 .. 100.00 sec;
Frequency Prot.
0.00 .. 100.00 sec;
Frequency Prot.
10.0 .. 125.0 V; 0
Frequency Prot.
0.10 .. 1.25 U/UnS;
0
Breaker Failure
OFF
ON
Block relay
Breaker Failure
0 .. 8
Breaker Failure
0 .. 24
Breaker Failure
0.00 .. 60.00 sec; ∞ 0.15 sec
Breaker Failure
0.00 .. 60.00 sec; ∞ 0.30 sec
Breaker Fail. 2
OFF
ON
Block relay
Breaker Fail. 2
0 .. 8
Breaker Fail. 2
0 .. 24
Breaker Fail. 2
0.00 .. 60.00 sec; ∞ 0.15 sec
Breaker Fail. 2
0.00 .. 60.00 sec; ∞ 0.30 sec
Functions, Settings, Information
Default Setting
Comments
T U>> Time Delay
0.98
U>, U>> Drop Out Ratio
U-ph-ph
Measurement Values
OFF
Over / Under Frequency
Protection
Pick-up frequency f<
Pick-up frequency f<<
Pick-up frequency f<<<
Pick-up frequency f>
Pick-up frequency f<
Pick-up frequency f<<
Pick-up frequency f<<<
Pick-up frequency f>
Pick-up frequency f<
Pick-up frequency f<<
Pick-up frequency f<<<
Pick-up frequency f>
20.00 sec
Delay time T f<
1.00 sec
Delay time T f<<
6.00 sec
Delay time T f<<<
10.00 sec
Delay time T f>
65.0 V
Minimum Required
Voltage for Operation
0.65 U/UnS
Minimum voltage
OFF
Breaker Failure Protection
0
Start with Relay (intern)
0
Start with Relay (intern)
T1, Delay of 1st stage
(local trip)
T2, Delay of 2nd stage
(busbar trip)
OFF
Breaker Failure Protection
0
Start with Relay (intern)
0
Start with Relay (intern)
T1, Delay of 1st stage
(local trip)
T2, Delay of 2nd stage
(busbar trip)
F.2 Settings
579