Siemens SIPROTEC 4 7UT6 Series Manual page 553

Differential protection
Table of Contents

Advertisement

Addr. Parameter
391
I PRIMARY OP 11
392
I PRIMARY OP 12
396
PHASE SELECTION
403
I PRIMARY OP M3
404
I PRIMARY OP M4
405
I PRIMARY OP M5
408
UN-PRI M3
409
UN-PRI U4
413
REF PROT. AT
414
REF PROT. 2 AT
420
DMT/IDMT Ph AT
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
Function
C
Setting Options
P.System Data
1 .. 100000 A
1
P.System Data
1 .. 100000 A
1
P.System Data
Phase 1
1
Phase 2
Phase 3
P.System Data
1 .. 100000 A
1
P.System Data
1 .. 100000 A
1
P.System Data
1 .. 100000 A
1
P.System Data
0.4 .. 800.0 kV
1
P.System Data
0.4 .. 800.0 kV
1
P.System Data
Side 1
1
Side 2
Side 3
Side 4
Side 5
auto-connected
n.assigMeasLoc3
n.assigMeasLoc4
n.assigMeasLoc5
P.System Data
Side 1
1
Side 2
Side 3
Side 4
Side 5
auto-connected
n.assigMeasLoc3
n.assigMeasLoc4
n.assigMeasLoc5
P.System Data
Side 1
1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Functions, Settings, Information
Default Setting
Comments
200 A
Primary Operating
Current End 11
200 A
Primary Operating
Current End 12
Phase 1
Phase selection
200 A
Primary Operating
Current Meas. Loc. 3
200 A
Primary Operating
Current Meas. Loc. 4
200 A
Primary Operating
Current Meas. Loc. 5
110.0 kV
Rated Primary Voltage
Measuring Loc. 3
110.0 kV
Rated Primary Voltage U4
Side 1
Restricted earth fault
prot. assigned to
Side 1
Restricted earth fault
prot2 assigned to
Side 1
DMT / IDMT Phase
assigned to
F.2 Settings