Mounting and Commissioning
3.1 Mounting and Connections
For 1-phase busbar protection:
Each input can be set individually. Only if measuring inputs Ι
plugged to the same rated current. Only if measuring inputs Ι
plugged to the same rated current.
If different rated currents are reigning within the input groups, the corresponding common jumper is
plugged to"undef".
For interposed summation transformers with 100 mA output, jumpers of all measuring inputs, including
the common jumpers, are plugged to 0.1 A.
Table 3-11
Application
3-phase
Ι
L1S1
Ι
L2S1
Ι
L3S1
Ι
L1S2
Ι
L2S2
Ι
L3S2
Ι
Z1
Ι
Z3
Input/Output Board(s) C-I/O-1 and C-I/O-10 (only 7UT633 and 7UT635)
The PCB layout for the C-I/O-1 input/output board is shown in
as from release 7UT6../EE in
326
Assignment of jumpers for the rated current to the measuring inputs
1-phase
Ι
1
Ι
2
Ι
3
Ι
4
Ι
5
Ι
6
Ι
7
Ι
8
Figure
3-10.
to Ι
have the same rated current, X68 is
1
3
to Ι
have the same rated current, X69 is
4
6
Jumpers
individual
X61
X62
X63
X65
X66
X67
X64
Figure 3-9
and the input/output group C-I/O-10
C53000-G1176-C230-5, Edition 09.2016
common
X68
X69
X70
SIPROTEC 4, 7UT6x, Manual