Jumper
Rated voltage
DC 24 V to 48 V
X55
not used
cannot be changed
Fuse
T4H250V
Table 3-6
Binary Inputs
BI1
BI2
BI3
BI4
BI5
1)
Factory settings for devices with rated power supply voltage DC 24 to 125 V
2)
Factory settings for devices with rated power supply voltage DC 110 to 220 V, AC 115 to 230 V to 250 V
3)
Only for control voltage DC 200 V or DC 250 V
Table 3-7
Jumper
X40
By repositioning jumpers the interface RS485 can be modified into a RS232 interface and vice versa.
Jumpers X105 to X110 must be set to the same position!
Table 3-8
Jumper
X103 and X104
X105 to X110
The jumpers are preset at the factory according to the configuration ordered.
With interface RS232 jumper X111 is needed to activate CTS which enables the communication with the
modem.
Table 3-9
Jumper
X111
1)
Delivery state
Jumper setting 2-3: The connection to the modem is usually established with a star coupler or fibre-optic
converter. Therefore the modem control signals according to RS232 standard DIN 66020 are not available.
Modem signals are not required since the connection to the SIPROTEC 4 devices is always operated in the half-
duplex mode. Please use the connection cable with order number 7XV5100-4.
Jumper setting 1-2: This setting makes the modem signals available, i. e. for a direct RS232-connection
between the SIPROTEC 4 device and the modem this setting can be selected optionally. We recommend to use
a standard RS232 modem connection cable (converter 9-pin to 25-pin).
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
DC 60 V to 125 V
not used
interchangeable
T2H250V
Jumper setting of the Pickup Voltages of the binary inputs BI1 to BI5 on the C-CPU-2
processor module
Jumper
Threshold 19 V
X21
1-2
X22
1-2
X23
1-2
X24
1-2
X25
1-2
Jumper setting of the quiescent state of the Life Contact on the processor board C-CPU-2
Open in the quiescent state
1-2
Jumper settings of the integrated RS232/RS485 Interface on the C-CPU-2 processor board
RS232
1-2
1-2
Jumper setting for CTS (Clear To Send, flow control) on the C-CPU-2 processor board
/CTS from interface RS232
1-2
DC 110 V to 250 V,
AC 115 V to 230 V
1-2
1)
Threshold 88 V
2)
2-3
2-3
2-3
2-3
2-3
Closed in the quiescent state
2-3
RS485
1-2
2-3
/CTS triggered by /RTS
2-3
1)
Mounting and Commissioning
3.1 Mounting and Connections
DC 220 V to 250 V,
AC 115 V to 230 V
1-2
Threshold 176 V
3)
3-4
3-4
3-4
3-4
3-4
Presetting
2-3
323