Siemens SIPROTEC 4 7UT6 Series Manual page 575

Differential protection
Table of Contents

Advertisement

Addr. Parameter
3922
T IEp
3923
D IEp
4001
UNBALANCE LOAD Unbalance Load
4011
I2>>
4012
I2>>
4013
T I2>>
4014
I2>
4015
I2>
4016
T I2>
4021
I2p
4022
I2p
4023
T I2p
4024
D I2p
4025
I2p DROP-OUT
4026
IEC CURVE
4027
ANSI CURVE
4031
I2>
4032
I2 tolerance
4033
T WARN
4034
FACTOR K
4035
T COOL DOWN
4201
THERM. OVERLOAD Therm. Over-
4202
K-FACTOR
4203
TIME CONSTANT
4204
Θ ALARM
4205
I ALARM
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
Function
C
Setting Options
Earth O/C 2
0.05 .. 3.20 sec; ∞
Earth O/C 2
0.50 .. 15.00 ; ∞
OFF
ON
Block relay
Unbalance Load 1A
0.10 .. 3.00 A; ∞
5A
0.50 .. 15.00 A; ∞
Unbalance Load
0.10 .. 3.00 I/InS; ∞ 0.50 I/InS
Unbalance Load
0.00 .. 60.00 sec; ∞ 1.50 sec
Unbalance Load 1A
0.10 .. 3.00 A; ∞
5A
0.50 .. 15.00 A; ∞
Unbalance Load
0.10 .. 3.00 I/InS; ∞ 0.10 I/InS
Unbalance Load
0.00 .. 60.00 sec; ∞ 1.50 sec
Unbalance Load 1A
0.10 .. 2.00 A
5A
0.50 .. 10.00 A
Unbalance Load
0.10 .. 2.00 I/InS
Unbalance Load
0.05 .. 3.20 sec; ∞
Unbalance Load
0.50 .. 15.00 ; ∞
Unbalance Load
Instantaneous
Disk Emulation
Unbalance Load
Normal Inverse
Very Inverse
Extremely Inv.
Unbalance Load
Extremely Inv.
Inverse
Moderately Inv.
Very Inverse
Unbalance Load 1A
0.01 .. 4.00 A; ∞
5A
0.05 .. 20.00 A; ∞
Unbalance Load
0.01 .. 0.80 I/InS; ∞ 0.16 I/InS
Unbalance Load
0.00 .. 60.00 sec; ∞ 20.00 sec
Unbalance Load
1.0 .. 100.0 sec; ∞
Unbalance Load
0 .. 50000 sec
OFF
load
ON
Block relay
Alarm Only
Therm. Over-
0.10 .. 4.00
load
Therm. Over-
1.0 .. 999.9 min
load
Therm. Over-
50 .. 100 %
load
Therm. Over-
0.10 .. 4.00 I/InS
load
Functions, Settings, Information
Default Setting
Comments
0.50 sec
T IEp Time Dial
5.00
D IEp Time Dial
OFF
Unbalance Load (Nega-
tive Sequence)
0.50 A
I2>> Pickup
2.50 A
I2>> Pickup
T I2>> Time Delay
0.10 A
I2> Pickup
0.50 A
I2> Pickup
T I2> Time Delay
0.90 A
I2p Pickup
4.50 A
0.90 I/InS
I2p Pickup
0.50 sec
T I2p Time Dial
5.00
D I2p Time Dial
Instantaneous
I2p Drop-out Character-
istic
Extremely Inv.
IEC Curve
Extremely Inv.
ANSI Curve
0.10 A
Continously Permissible
Current I2
0.50 A
Permissable quiescent
unbalanced load
Warning Stage Time
Delay
18.7 sec
Negativ Sequence Factor
K
1650 sec
Time for Cooling Down
OFF
Thermal Overload Protec-
tion
1.10
K-Factor
100.0 min
Thermal Time Constant
90 %
Thermal Alarm Stage
1.00 I/InS
Current Overload Alarm
Setpoint
F.2 Settings
575