Siemens SIPROTEC 4 7UT6 Series Manual page 582

Differential protection
Table of Contents

Advertisement

Functions, Settings, Information
F.2 Settings
Addr. Parameter
9011A RTD 1 TYPE
9012A RTD 1 LOCATION
9013
RTD 1 STAGE 1
9014
RTD 1 STAGE 1
9015
RTD 1 STAGE 2
9016
RTD 1 STAGE 2
9021A RTD 2 TYPE
9022A RTD 2 LOCATION
9023
RTD 2 STAGE 1
9024
RTD 2 STAGE 1
9025
RTD 2 STAGE 2
9026
RTD 2 STAGE 2
9031A RTD 3 TYPE
9032A RTD 3 LOCATION
9033
RTD 3 STAGE 1
9034
RTD 3 STAGE 1
9035
RTD 3 STAGE 2
582
Function
C
Setting Options
RTD-Box
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
RTD-Box
Oil
Ambient
Winding
Bearing
Other
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
RTD-Box
Oil
Ambient
Winding
Bearing
Other
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
RTD-Box
Oil
Ambient
Winding
Bearing
Other
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
-50 .. 250 °C; ∞
Default Setting
Comments
Pt 100 Ω
RTD 1: Type
Oil
RTD 1: Location
100 °C
RTD 1: Temperature Stage
1 Pickup
212 °F
RTD 1: Temperature Stage
1 Pickup
120 °C
RTD 1: Temperature Stage
2 Pickup
248 °F
RTD 1: Temperature Stage
2 Pickup
Not connected
RTD 2: Type
Other
RTD 2: Location
100 °C
RTD 2: Temperature Stage
1 Pickup
212 °F
RTD 2: Temperature Stage
1 Pickup
120 °C
RTD 2: Temperature Stage
2 Pickup
248 °F
RTD 2: Temperature Stage
2 Pickup
Not connected
RTD 3: Type
Other
RTD 3: Location
100 °C
RTD 3: Temperature Stage
1 Pickup
212 °F
RTD 3: Temperature Stage
1 Pickup
120 °C
RTD 3: Temperature Stage
2 Pickup
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016

Hide quick links: