Siemens SIPROTEC 4 7UT6 Series Manual page 212

Differential protection
Table of Contents

Advertisement

Functions
2.10 RTD-Boxes for Overload Detection
Addr.
Parameter
9012A
RTD 1 LOCATION
9013
RTD 1 STAGE 1
9014
RTD 1 STAGE 1
9015
RTD 1 STAGE 2
9016
RTD 1 STAGE 2
9021A
RTD 2 TYPE
9022A
RTD 2 LOCATION
9023
RTD 2 STAGE 1
9024
RTD 2 STAGE 1
9025
RTD 2 STAGE 2
9026
RTD 2 STAGE 2
9031A
RTD 3 TYPE
9032A
RTD 3 LOCATION
9033
RTD 3 STAGE 1
9034
RTD 3 STAGE 1
9035
RTD 3 STAGE 2
9036
RTD 3 STAGE 2
212
Setting Options
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
Default Setting
Comments
Oil
RTD 1: Location
100 °C
RTD 1: Temperature Stage 1
Pickup
212 °F
RTD 1: Temperature Stage 1
Pickup
120 °C
RTD 1: Temperature Stage 2
Pickup
248 °F
RTD 1: Temperature Stage 2
Pickup
Not connected
RTD 2: Type
Other
RTD 2: Location
100 °C
RTD 2: Temperature Stage 1
Pickup
212 °F
RTD 2: Temperature Stage 1
Pickup
120 °C
RTD 2: Temperature Stage 2
Pickup
248 °F
RTD 2: Temperature Stage 2
Pickup
Not connected
RTD 3: Type
Other
RTD 3: Location
100 °C
RTD 3: Temperature Stage 1
Pickup
212 °F
RTD 3: Temperature Stage 1
Pickup
120 °C
RTD 3: Temperature Stage 2
Pickup
248 °F
RTD 3: Temperature Stage 2
Pickup
C53000-G1176-C230-5, Edition 09.2016