Siemens SIPROTEC 4 7UT6 Series Manual page 331

Differential protection
Table of Contents

Advertisement

The relay contacts for binary outputs BO1 through BO5 can be connected to common potential, or configured
individually for BO1, BO4 and BO5 (BO2 and BO3 are without function in this context) (see also General
Diagrams in the Appendix
Table 3-16
Jumper
X80
X81
X82
1)
Delivery state
Jumpers X71 through X73 on the input/output board C-I/O-2 serve for setting the bus address. Their position
may not be changed. The following table shows the preset jumper positions.
Table 3-17
Jumper
Presetting
X71
1-2 (H)
X72
1-2 (H)
X73
2-3 (L)
The rated currents of the measured current inputs can be determined for each analogue input via jumpers.
With default settings all jumpers are set to the same rated current (according to the order number of the
device).
The input/output board C-I/O-2 carries the following measured current inputs:
For 3-phase applications and 1-phase transformers:
There are 3 measuring inputs for the three-phase measuring location M3: Ι
X61, X62, X63 belonging to this measuring location must be plugged all to the rated secondary current
of the connected current transformers: "1A" or "5A"). Furthermore, the corresponding common jumpers
(X51 and X60) have to be plugged to the same rated current.
For 1-phase busbar protection:
There are 3 measuring inputs for 3 different measuring locations, i.e. the feeders 7 to 9: Ι
input can be set individually (X61, X62, X63) to "1A", "5A" or "0.1A". Only if the measuring inputs Ι7 to Ι9
have the same rated current, the common jumpers X60 are plugged to this rated current.
If different rated currents (X51 and X60) are reigning within the input group, the position of the common
jumpers (X51 and X60) is irrelevant.
For the additional single-phase measuring input Ι
Jumper X64 is set to the required rated current for this 1-phase current input: "1A" oder "5A".
Table 3-18
Jumper
X51
X60
X61
X62
X63
X64
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
B Terminal
Assignments).
Jumper settings for the configuration of the Common Potential of BO1 through BO5 or for
configuration of BO1, BO4 and BO5 as Single Relays
BO1 to BO5
connected to common potential
1-2, 3-4
1-2, 3-4
2-3
Jumper Position of the Module Addresses of the input/output board C-I/O-2
Jumper setting for Rated current or Measuring range
Rated current 0.1 A
Measuring range 10 A
2-3
1-2
1-5
1-5
1-5
1-5
BO1, BO4, BO5 configured as single
relays
1)
(BO2 and BO3 without function)
2-3, 4-5
2-3, 4-5
1-2
:
Z2
Rated current 1 A
Measuring range 100 A
1-2
1-2
3-5
3-5
3-5
3-5
Mounting and Commissioning
3.1 Mounting and Connections
, Ι
, Ι
. The jumpers
L1M3
L2M3
L3M3
, Ι
, Ι
. Each
7
8
9
Rated current 5 A
Measuring range 500 A
1-2
2-3
4-5
4-5
4-5
4-5
331