Functions, Settings, Information
F.2 Settings
Addr. Parameter
3801
EARTH O/C
3802
InRushRestEarth
3808A IE MAN. CLOSE
3811
IE>>
3812
T IE>>
3813
IE>
3814
T IE>
3821
IEp
3822
T IEp
3823
D IEp
3824
TOC DROP-OUT
3825
IEC CURVE
3826
ANSI CURVE
3831
I/IEp PU T/TEp
3832
MofPU Res T/TEp
3841
2.HARM. Earth
3842
I Max InRr. E
3911
IE>>
3912
T IE>>
3913
IE>
3914
T IE>
3921
IEp
574
Function
C
Setting Options
Earth O/C 2
ON
OFF
Block relay
Earth O/C 2
ON
OFF
Earth O/C 2
IE>> instant.
IE> instant.
IEp instant.
Inactive
Earth O/C 2
1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞ 5.00 A
Earth O/C 2
0.00 .. 60.00 sec; ∞ 1.50 sec
Earth O/C 2
1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞ 2.00 A
Earth O/C 2
0.00 .. 60.00 sec; ∞ 2.00 sec
Earth O/C 2
1A
0.05 .. 4.00 A
5A
0.25 .. 20.00 A
Earth O/C 2
0.05 .. 3.20 sec; ∞
Earth O/C 2
0.50 .. 15.00 ; ∞
Earth O/C 2
Instantaneous
Disk Emulation
Earth O/C 2
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Earth O/C 2
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Earth O/C 2
1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
Earth O/C 2
0.05 .. 0.95 I/Ip; ∞
0.01 .. 999.00 TD
Earth O/C 2
10 .. 45 %
Earth O/C 2
1A
0.30 .. 25.00 A
5A
1.50 .. 125.00 A
Earth O/C 2
1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞ 35.00 A
Earth O/C 2
0.00 .. 60.00 sec; ∞ 1.50 sec
Earth O/C 2
1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞ 7.50 A
Earth O/C 2
0.00 .. 60.00 sec; ∞ 2.00 sec
Earth O/C 2
1A
0.05 .. 4.00 A
5A
0.25 .. 20.00 A
Default Setting
Comments
OFF
Earth Time Overcurrent
OFF
InRush Restrained O/C
Earth
IE>> instant.
O/C IE Manual Close
Mode
1.00 A
IE>> Pickup
T IE>> Time Delay
0.40 A
IE> Pickup
T IE> Time Delay
0.40 A
IEp Pickup
2.00 A
0.50 sec
T IEp Time Dial
5.00
D IEp Time Dial
Disk Emulation
TOC Drop-out Character-
istic
Normal Inverse
IEC Curve
Very Inverse
ANSI Curve
Pickup Curve IE/IEp - TIE/
TIEp
Multiple of Pickup <-> TI/
TIEp
15 %
2nd harmonic O/C E in %
of fundamental
7.50 A
Maximum Current for Inr.
Rest. O/C Earth
37.50 A
7.00 A
IE>> Pickup
T IE>> Time Delay
1.50 A
IE> Pickup
T IE> Time Delay
1.00 A
IEp Pickup
5.00 A
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016