Differential protection
Table of Contents

Advertisement

Introduction
1.3 Characteristics
High level of stability even with different degrees of current transformer saturation
Monitoring of the current connections with operation currents
Busbar Protection
Single-phase differential protection for a busbar with up to 7 or 9 or 12 feeders (depending on the
variant ordered)
Either one relay per phase or one relay connected via interposed summation current transformers
Tripping characteristic with current restraint
Short tripping time
Insensitivity to DC components and current transformer saturation
High level of stability even with different degrees of current transformer saturation
Monitoring of the current connections with operation currents.
Earth Fault Differential Protection
Earth fault protection for earthed transformer windings, generators, motors, shunt reactors, or starpoint
formers
Short command duration
High sensitivity for earth faults within the protected zone
High stability against external earth faults using the magnitude and phase relationship of through-
flowing earth current
2 restricted earth fault protection functions possible (only 7UT613/63x)
High-impedance Differential Protection
Highly sensitive fault current detection using a common (external) burden resistor
Short tripping time
Insensitive against DC components and current transformer saturation
High stability with optimum matching
Suitable for earth fault detection on earthed generators, motors, shunt reactors, and transformers,
including auto-transformers, with or without earthed starpoint
Suitable for any voltage measurement (via the resistor current) for application of high-impedance unit
protection
Tank Leakage Protection
For transformers or reactors the tank of which is installed isolated or with high resistance
Monitoring of the current flowing between the tank and ground
Can be connected via a „normal" current input of the device or the special highly sensitive current input
(3 mA smallest setting)
Earth Fault Differential Protection
Earth fault protection for earthed transformer windings, generators, motors, shunt reactors, or starpoint
formers
Short command duration
High sensitivity for earth faults within the protected zone
22
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016