Siemens SIPROTEC 4 7UT6 Series Manual page 568

Differential protection
Table of Contents

Advertisement

Functions, Settings, Information
F.2 Settings
Addr. Parameter
2442
I Max InRr. E
2511
IE>>
2512
T IE>>
2513
IE>
2514
T IE>
2521
IEp
2522
T IEp
2523
D IEp
2701
1Phase O/C
2702
1Phase I>>
2703
1Phase I>>
2704
T 1Phase I>>
2705
1Phase I>
2706
1Phase I>
2707
T 1Phase I>
2911A FFM U>(min)
3001
PHASE O/C
3002
InRushRest. Ph
3008A MANUAL CLOSE
3011
I>>
3012
I>>
3013
T I>>
3014
I>
3015
I>
3016
T I>
3021
Ip
568
Function
C
Setting Options
Earth O/C
1A
0.30 .. 25.00 A
5A
1.50 .. 125.00 A
Earth O/C
1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞ 35.00 A
Earth O/C
0.00 .. 60.00 sec; ∞ 1.50 sec
Earth O/C
1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞ 7.50 A
Earth O/C
0.00 .. 60.00 sec; ∞ 2.00 sec
Earth O/C
1A
0.05 .. 4.00 A
5A
0.25 .. 20.00 A
Earth O/C
0.05 .. 3.20 sec; ∞
Earth O/C
0.50 .. 15.00 ; ∞
1Phase O/C
OFF
ON
Block relay
1Phase O/C
1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞ 2.50 A
1Phase O/C
0.003 .. 1.500 A; ∞ 0.300 A
1Phase O/C
0.00 .. 60.00 sec; ∞ 0.10 sec
1Phase O/C
1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞ 1.00 A
1Phase O/C
0.003 .. 1.500 A; ∞ 0.100 A
1Phase O/C
0.00 .. 60.00 sec; ∞ 0.50 sec
Supervision
10 .. 100 V
Phase O/C 2
ON
OFF
Block relay
Phase O/C 2
ON
OFF
Phase O/C 2
I>> instant.
I> instant.
Ip instant.
Inactive
Phase O/C 2
1A
0.10 .. 35.00 A; ∞
5A
0.50 .. 175.00 A; ∞ 20.00 A
Phase O/C 2
0.10 .. 35.00 I/InS;
Phase O/C 2
0.00 .. 60.00 sec; ∞ 0.10 sec
Phase O/C 2
1A
0.10 .. 35.00 A; ∞
5A
0.50 .. 175.00 A; ∞ 10.00 A
Phase O/C 2
0.10 .. 35.00 I/InS;
Phase O/C 2
0.00 .. 60.00 sec; ∞ 0.30 sec
Phase O/C 2
1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
Default Setting
Comments
7.50 A
Maximum Current for Inr.
Rest. O/C Earth
37.50 A
7.00 A
IE>> Pickup
T IE>> Time Delay
1.50 A
IE> Pickup
T IE> Time Delay
1.00 A
IEp Pickup
5.00 A
0.50 sec
T IEp Time Dial
5.00
D IEp Time Dial
OFF
1Phase Time Overcurrent
0.50 A
1Phase O/C I>> Pickup
1Phase O/C I>> Pickup
T 1Phase O/C I>> Time
Delay
0.20 A
1Phase O/C I> Pickup
1Phase O/C I> Pickup
T 1Phase O/C I> Time
Delay
20 V
Minimum Voltage
Threshold U>
OFF
Phase Time Overcurrent
OFF
InRush Restrained O/C
Phase
I>> instant.
O/C Manual Close Mode
4.00 A
I>> Pickup
4.00 I/InS
I>> Pickup
T I>> Time Delay
2.00 A
I> Pickup
2.00 I/InS
I> Pickup
T I> Time Delay
2.00 A
Ip Pickup
10.00 A
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016