Siemens SIPROTEC 4 7UT6 Series Manual page 571

Differential protection
Table of Contents

Advertisement

Addr. Parameter
3311
I>>
3312
I>>
3313
T I>>
3314
I>
3315
I>
3316
T I>
3321
Ip
3322
Ip
3323
T Ip
3324
D Ip
3401
3I0 O/C
3402
InRushRest. 3I0
3408A 3I0 MAN. CLOSE
3411
3I0>>
3412
3I0>>
3413
T 3I0>>
3414
3I0>
3415
3I0>
3416
T 3I0>
3421
3I0p
3422
3I0p
3423
T 3I0p
3424
D 3I0p
3425
TOC DROP-OUT
3426
IEC CURVE
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
Function
C
Setting Options
Phase O/C 3
1A
0.10 .. 35.00 A; ∞
5A
0.50 .. 175.00 A; ∞ 50.00 A
Phase O/C 3
0.10 .. 35.00 I/InS;
Phase O/C 3
0.00 .. 60.00 sec; ∞ 0.10 sec
Phase O/C 3
1A
0.10 .. 35.00 A; ∞
5A
0.50 .. 175.00 A; ∞ 20.00 A
Phase O/C 3
0.10 .. 35.00 I/InS;
Phase O/C 3
0.00 .. 60.00 sec; ∞ 0.30 sec
Phase O/C 3
1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
Phase O/C 3
0.10 .. 4.00 I/InS
Phase O/C 3
0.05 .. 3.20 sec; ∞
Phase O/C 3
0.50 .. 15.00 ; ∞
3I0 O/C 2
ON
OFF
Block relay
3I0 O/C 2
ON
OFF
3I0 O/C 2
3I0>> instant.
3I0> instant.
3I0p instant.
Inactive
3I0 O/C 2
1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞ 5.00 A
3I0 O/C 2
0.05 .. 35.00 I/InS;
3I0 O/C 2
0.00 .. 60.00 sec; ∞ 1.50 sec
3I0 O/C 2
1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞ 2.00 A
3I0 O/C 2
0.05 .. 35.00 I/InS;
3I0 O/C 2
0.00 .. 60.00 sec; ∞ 2.00 sec
3I0 O/C 2
1A
0.05 .. 4.00 A
5A
0.25 .. 20.00 A
3I0 O/C 2
0.05 .. 4.00 I/InS
3I0 O/C 2
0.05 .. 3.20 sec; ∞
3I0 O/C 2
0.50 .. 15.00 ; ∞
3I0 O/C 2
Instantaneous
Disk Emulation
3I0 O/C 2
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Functions, Settings, Information
Default Setting
Comments
10.00 A
I>> Pickup
10.00 I/InS
I>> Pickup
T I>> Time Delay
4.00 A
I> Pickup
4.00 I/InS
I> Pickup
T I> Time Delay
4.00 A
Ip Pickup
20.00 A
4.00 I/InS
Ip Pickup
0.50 sec
T Ip Time Dial
5.00
D Ip Time Dial
OFF
3I0 Time Overcurrent
OFF
InRush Restrained O/C 3I0
3I0>> instant.
O/C 3I0 Manual Close
Mode
1.00 A
3I0>> Pickup
1.00 I/InS
3I0>> Pickup
T 3I0>> Time Delay
0.40 A
3I0> Pickup
0.40 I/InS
3I0> Pickup
T 3I0> Time Delay
0.40 A
3I0p Pickup
2.00 A
0.40 I/InS
3I0p Pickup
0.50 sec
T 3I0p Time Dial
5.00
D 3I0p Time Dial
Disk Emulation
TOC Drop-out Character-
istic
Normal Inverse
IEC Curve
F.2 Settings
571

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents