Siemens SIPROTEC 4 7UT6 Series Manual page 260

Differential protection
Table of Contents

Advertisement

Functions
2.19 Monitoring Functions
TR
Trip relay contact
CB
Circuit breaker
TC
Circuit breaker trip coil
Aux1
Circuit breaker auxiliary contact (make)
Aux2
Circuit breaker auxiliary contact (break)
U-CTR
Control voltage (trip voltage)
U-BI1
Input voltage of 1st binary input
U-BI2
Input voltage of 2nd binary input
The diagram shows the circuit breaker in closed state.
Depending on the state of the trip relay and the circuit breaker s auxiliary contacts, the binary inputs are trig-
gered (logical state "H" in the following table) or short-circuited (logical state and "L").
The state where both binary inputs are not activated ("L"), is only possible during a short transition phase in
intact trip circuits (command relay has issued trip command, but the CB has not yet opened).
A continuous state of this condition is only possible when the trip circuit has been interrupted, a short-circuit
exists in the trip circuit, or battery voltage failure occurs. It is thus used as a monitoring criterion.
Table 2-11
No.
Trip relay
contact
1
open
2
open
3
closed
4
closed
The conditions of the two binary inputs are checked periodically. A query takes place about every 500 ms.
Only after n = 3 of these consecutive state queries have detected a fault, an alarm is given. The repeated
measurements determine the delay of the alarm message and avoid that an alarm is output during short tran-
sition periods. After the fault in the trip circuit is removed, the alarm is reset automatically after the same
time.
[ausloeselogik-mit-2be-121102-st, 1, en_GB]
Figure 2-119
Supervision Using One Binary Input
The binary input is connected in parallel to the respective command relay contact of the protection device
according to
Figure
tute resistor R.
The control voltage for the circuit breaker should be at least double the size of the minimum voltage drops at
the binary input (U
with a system control voltage of over 38 V.
An calculation example for the substitute resistance of R is shown in the Section "Mounting and Commis-
sioning".
260
Status table of the binary inputs depending on command relay and circuit breaker switching
state
Circuit breaker
ON
OFF
ON
OFF
Logic Diagram of the Trip Circuit Supervision with Two Binary Inputs (simplified)
2-120. The circuit breaker auxiliary contact is bridged with the help of a high-ohmic substi-
> 2 · U
). Since at least 19 V are needed for the binary input, the monitor can be used
Ctr
BImin
Aux.1
Aux.2
closed
open
open
closed
closed
open
open
closed
C53000-G1176-C230-5, Edition 09.2016
BI 1
BI 2
H
L
H
H
L
L
L
H
SIPROTEC 4, 7UT6x, Manual