Siemens SIPROTEC 4 7UT6 Series Manual page 324

Differential protection
Table of Contents

Advertisement

Mounting and Commissioning
3.1 Mounting and Connections
NOTE
i
i
For a direct connection to DIGSI with interface RS232 jumper X111 must be plugged in position 2-3.
If there are no external terminating resistors in the system, the last devices on a RS485 bus must be config-
ured via jumpers X103 and X104.
Table 3-10
Jumper
X103
X104
Note: Both jumpers must always be plugged in the same way!
When the device is delivered from the factory, the terminating resistors are disconnected (jumper setting 1-2).
The terminating resistors can also be connected externally (e.g. to the connection module as illustrated in
Figure
Figure
3-19). In that case the terminating resistors provided on the C-CPU- 2 processor board must be
switched off.
Jumper X90 has no function. The factory setting is 1-2.
324
Jumper settings of the Terminating Resistors of the RS485 interface on the C-CPU-2 processor
board
Terminating Resistor
enabled
2-3
2-3
Terminating resistor
disabled
1-2
1-2
C53000-G1176-C230-5, Edition 09.2016
Presetting
1-2
1-2
SIPROTEC 4, 7UT6x, Manual