Siemens SIPROTEC 4 7UT6 Series Manual page 570

Differential protection
Table of Contents

Advertisement

Functions, Settings, Information
F.2 Settings
Addr. Parameter
3202
InRushRest. Ph
3208A MANUAL CLOSE
3211
I>>
3212
I>>
3213
T I>>
3214
I>
3215
I>
3216
T I>
3221
Ip
3222
Ip
3223
T Ip
3224
D Ip
3225
TOC DROP-OUT
3226
IEC CURVE
3227
ANSI CURVE
3231
I/Ip PU T/Tp
3232
MofPU Res T/Tp
3241
2.HARM. Phase
3242
I Max InRr. Ph.
3243
I Max InRr. Ph.
3244
CROSS BLK.Phase
3245
T CROSS BLK.Ph
570
Function
C
Setting Options
Phase O/C 3
ON
OFF
Phase O/C 3
I>> instant.
I> instant.
Ip instant.
Inactive
Phase O/C 3
1A
0.10 .. 35.00 A; ∞
5A
0.50 .. 175.00 A; ∞ 20.00 A
Phase O/C 3
0.10 .. 35.00 I/InS;
Phase O/C 3
0.00 .. 60.00 sec; ∞ 0.10 sec
Phase O/C 3
1A
0.10 .. 35.00 A; ∞
5A
0.50 .. 175.00 A; ∞ 10.00 A
Phase O/C 3
0.10 .. 35.00 I/InS;
Phase O/C 3
0.00 .. 60.00 sec; ∞ 0.30 sec
Phase O/C 3
1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
Phase O/C 3
0.10 .. 4.00 I/InS
Phase O/C 3
0.05 .. 3.20 sec; ∞
Phase O/C 3
0.50 .. 15.00 ; ∞
Phase O/C 3
Instantaneous
Disk Emulation
Phase O/C 3
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Phase O/C 3
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Phase O/C 3
1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
Phase O/C 3
0.05 .. 0.95 I/Ip; ∞
0.01 .. 999.00 TD
Phase O/C 3
10 .. 45 %
Phase O/C 3
1A
0.30 .. 25.00 A
5A
1.50 .. 125.00 A
Phase O/C 3
0.30 .. 25.00 I/InS
Phase O/C 3
NO
YES
Phase O/C 3
0.00 .. 180.00 sec
Default Setting
Comments
OFF
InRush Restrained O/C
Phase
I>> instant.
O/C Manual Close Mode
4.00 A
I>> Pickup
4.00 I/InS
I>> Pickup
T I>> Time Delay
2.00 A
I> Pickup
2.00 I/InS
I> Pickup
T I> Time Delay
2.00 A
Ip Pickup
10.00 A
2.00 I/InS
Ip Pickup
0.50 sec
T Ip Time Dial
5.00
D Ip Time Dial
Disk Emulation
TOC Drop-out character-
istic
Normal Inverse
IEC Curve
Very Inverse
ANSI Curve
Pickup Curve I/Ip - TI/TIp
Multiple of Pickup <->
TI/TIp
15 %
2nd harmonic O/C Ph. in
% of fundamental
7.50 A
Maximum Current for Inr.
Rest. O/C Phase
37.50 A
7.50 I/InS
Maximum Current for Inr.
Rest. O/C Phase
NO
CROSS BLOCK O/C Phase
0.00 sec
CROSS BLOCK Time O/C
Phase
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016

Hide quick links:

Advertisement

Table of Contents
loading