Introduction
1.3 Characteristics
With or without including the ambient or coolant temperature (by means of external resistance tempera-
ture detector via RTD-box)
Alternative evaluation of the hot-spot temperature according to IEC 60354 with calculation of the reserve
power and ageing rate (by means of external resistance temperature detector via RTD-box)
2 overload protection functions possible (only 7UT613/63x)
Overexcitation protection (only 7UT613 and 7UT633)
Processing of the voltage/frequency ration U/f, which represents the induction B of a shunt reactance
(transformer, shunt reactor)
Adjustable warning and tripping stage (with independent delay time)
Inverse standard characteristic or user-defined trip characteristic for calculation of the thermal stress,
selectable
Reverse power protection (only 7UT613 and 7UT633)
Real power calculation from positive sequence components
Short operating time or exact calculation of the active power via 16 cycles
Exact real power calculation for small power factor by compensating the error angle of the measuring
locations
Insensitive to power fluctuations
Short-time stage with external criteria, e.g. with closed emergency tripping
Forward power supervision (only 7UT613 and 7UT633)
Real power calculation from positive sequence components
Supervision of overvoltage (P>) or undervoltage (P<) of power with individually adjustable power limits
Short operating time or exact calculation of the active power via 16 cycles
Automatic blocking of stage P< for recognised measured voltage failure or wire break in CT secondary
circuit
Undervoltage protection (only 7UT613 and 7UT633)
Two-stage 3-phase undervoltage measurement
Evaluation of positive sequence component of the connected voltages, therefore independent of asym-
metries
Automatic blocking for measuring voltage failure
Adjustable dropout ratio
Overvoltage protection (only 7UT613 and 7UT633)
Two-stage 3-phase overvoltage measurement
Evaluation of the largest of the three phase-to-ground voltages or the largest of the three phase-to-phase
voltages (largest of the three phase-to-phase voltages (can be set)
Adjustable dropout ratio
Frequency protection (only 7UT613 and 7UT633)
Three underfrequency stages and one overfrequency stage
Frequency measurement via the positive sequence component of the voltages
24
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016