Siemens SIPROTEC 4 7UT6 Series Manual page 566

Differential protection
Table of Contents

Advertisement

Functions, Settings, Information
F.2 Settings
Addr. Parameter
2208A 3I0 MAN. CLOSE
2211
3I0>>
2212
3I0>>
2213
T 3I0>>
2214
3I0>
2215
3I0>
2216
T 3I0>
2221
3I0p
2222
3I0p
2223
T 3I0p
2224
D 3I0p
2225
TOC DROP-OUT
2226
IEC CURVE
2227
ANSI CURVE
2231
I/I0p PU T/TI0p
2232
MofPU ResT/TI0p
2241
2.HARM. 3I0
2242
I Max InRr. 3I0
2243
I Max InRr. 3I0
2311
3I0>>
2312
3I0>>
2313
T 3I0>>
566
Function
C
Setting Options
3I0 O/C
3I0>> instant.
3I0> instant.
3I0p instant.
Inactive
3I0 O/C
1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞ 5.00 A
3I0 O/C
0.05 .. 35.00 I/InS;
3I0 O/C
0.00 .. 60.00 sec; ∞ 1.50 sec
3I0 O/C
1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞ 2.00 A
3I0 O/C
0.05 .. 35.00 I/InS;
3I0 O/C
0.00 .. 60.00 sec; ∞ 2.00 sec
3I0 O/C
1A
0.05 .. 4.00 A
5A
0.25 .. 20.00 A
3I0 O/C
0.05 .. 4.00 I/InS
3I0 O/C
0.05 .. 3.20 sec; ∞
3I0 O/C
0.50 .. 15.00 ; ∞
3I0 O/C
Instantaneous
Disk Emulation
3I0 O/C
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
3I0 O/C
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
3I0 O/C
1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
3I0 O/C
0.05 .. 0.95 I/Ip; ∞
0.01 .. 999.00 TD
3I0 O/C
10 .. 45 %
3I0 O/C
1A
0.30 .. 25.00 A
5A
1.50 .. 125.00 A
3I0 O/C
0.30 .. 25.00 I/InS
3I0 O/C
1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞ 35.00 A
3I0 O/C
0.05 .. 35.00 I/InS;
3I0 O/C
0.00 .. 60.00 sec; ∞ 1.50 sec
Default Setting
Comments
3I0>> instant.
O/C 3I0 Manual Close
Mode
1.00 A
3I0>> Pickup
1.00 I/InS
3I0>> Pickup
T 3I0>> Time Delay
0.40 A
3I0> Pickup
0.40 I/InS
3I0> Pickup
T 3I0> Time Delay
0.40 A
3I0p Pickup
2.00 A
0.40 I/InS
3I0p Pickup
0.50 sec
T 3I0p Time Dial
5.00
D 3I0p Time Dial
Disk Emulation
TOC Drop-out Character-
istic
Normal Inverse
IEC Curve
Very Inverse
ANSI Curve
Pickup Curve 3I0/3I0p -
T3I0/T3I0p
Multiple of Pickup <->
T3I0/T3I0p
15 %
2nd harmonic O/C 3I0 in
% of fundamental
7.50 A
Maximum Current for Inr.
Rest. O/C 3I0
37.50 A
7.50 I/InS
Maximum Current for Inr.
Rest. O/C 3I0
7.00 A
3I0>> Pickup
7.00 I/InS
3I0>> Pickup
T 3I0>> Time Delay
SIPROTEC 4, 7UT6x, Manual