Siemens SIPROTEC 4 7UT6 Series Manual page 576

Differential protection
Table of Contents

Advertisement

Functions, Settings, Information
F.2 Settings
Addr. Parameter
4207A Kτ-FACTOR
4208A T EMERGENCY
4209A I MOTOR START
4210
TEMPSENSOR RTD
4211
TEMPSENSOR RTD
4212
TEMP. RISE I
4213
TEMP. RISE I
4220
OIL-DET. RTD
4221
OIL Sensor RTD
4222
HOT SPOT ST. 1
4223
HOT SPOT ST. 1
4224
HOT SPOT ST. 2
4225
HOT SPOT ST. 2
4226
AG. RATE ST. 1
4227
AG. RATE ST. 2
4231
METH. COOLING
4232
Y-WIND.EXPONENT Therm. Over-
4233
HOT-SPOT GR
4301
OVEREXC. PROT.
4302
U/f >
4303
T U/f >
4304
U/f >>
4305
T U/f >>
4306
t(U/f=1.05)
4307
t(U/f=1.10)
4308
t(U/f=1.15)
4309
t(U/f=1.20)
4310
t(U/f=1.25)
4311
t(U/f=1.30)
576
Function
C
Setting Options
Therm. Over-
1.0 .. 10.0
load
Therm. Over-
10 .. 15000 sec
load
Therm. Over-
0.60 .. 10.00 I/InS;
load
Therm. Over-
1 .. 6
load
Therm. Over-
1 .. 12
load
Therm. Over-
40 .. 200 °C
load
Therm. Over-
104 .. 392 °F
load
Therm. Over-
1 .. 6
load
Therm. Over-
1 .. 12
load
Therm. Over-
98 .. 140 °C
load
Therm. Over-
208 .. 284 °F
load
Therm. Over-
98 .. 140 °C
load
Therm. Over-
208 .. 284 °F
load
Therm. Over-
0.200 .. 128.000
load
Therm. Over-
0.200 .. 128.000
load
Therm. Over-
ON
load
OF
OD
1.6 .. 2.0
load
Therm. Over-
22 .. 29
load
Overexcit.
OFF
ON
Block relay
Overexcit.
1.00 .. 1.20
Overexcit.
0.00 .. 60.00 sec; ∞ 10.00 sec
Overexcit.
1.00 .. 1.40
Overexcit.
0.00 .. 60.00 sec; ∞ 1.00 sec
Overexcit.
0 .. 20000 sec
Overexcit.
0 .. 20000 sec
Overexcit.
0 .. 20000 sec
Overexcit.
0 .. 20000 sec
Overexcit.
0 .. 20000 sec
Overexcit.
0 .. 20000 sec
Default Setting
Comments
1.0
Kt-FACTOR when motor
stops
100 sec
Emergency Time
∞ I/InS
Current Pickup Value of
Motor Starting
1
Temperature sensor
connected to RTD
1
Temperature sensor
connected to RTD
100 °C
Temperature Rise at
Rated Sec. Curr.
212 °F
Temperature Rise at
Rated Sec. Curr.
1
Oil-Detector conected at
RTD
1
Oil sensor connected to
RTD
98 °C
Hot Spot Temperature
Stage 1 Pickup
208 °F
Hot Spot Temperature
Stage 1 Pickup
108 °C
Hot Spot Temperature
Stage 2 Pickup
226 °F
Hot Spot Temperature
Stage 2 Pickup
1.000
Aging Rate STAGE 1
Pickup
2.000
Aging Rate STAGE 2
Pickup
ON
Method of Cooling
1.6
Y-Winding Exponent
22
Hot-spot to top-oil
gradient
OFF
Overexcitation Protection
(U/f)
1.10
U/f > Pickup
T U/f > Time Delay
1.40
U/f >> Pickup
T U/f >> Time Delay
20000 sec
U/f = 1.05 Time Delay
6000 sec
U/f = 1.10 Time Delay
240 sec
U/f = 1.15 Time Delay
60 sec
U/f = 1.20 Time Delay
30 sec
U/f = 1.25 Time Delay
19 sec
U/f = 1.30 Time Delay
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016