Siemens SIPROTEC 4 7UT6 Series Manual page 564

Differential protection
Table of Contents

Advertisement

Functions, Settings, Information
F.2 Settings
Addr. Parameter
1702
Start CLP Phase
1703
Start CLP 3I0
1704
Start CLP Earth
1705
Start CLP Ph 2
1706
Start CLP Ph 3
1707
Start CLP 3I0 2
1708
Start CLP 3I0 3
1709
Start CLP E 2
1711
CB Open Time
1712
Active Time
1713
Stop Time
2001
PHASE O/C
2002
InRushRest. Ph
2008A MANUAL CLOSE
2011
I>>
2012
I>>
2013
T I>>
2014
I>
2015
I>
2016
T I>
2021
Ip
2022
Ip
2023
T Ip
2024
D Ip
2025
TOC DROP-OUT
564
Function
C
Setting Options
ColdLoadPickup
No Current
Breaker Contact
ColdLoadPickup
No Current
Breaker Contact
ColdLoadPickup
No Current
Breaker Contact
ColdLoadPickup
No Current
Breaker Contact
ColdLoadPickup
No Current
Breaker Contact
ColdLoadPickup
No Current
Breaker Contact
ColdLoadPickup
No Current
Breaker Contact
ColdLoadPickup
No Current
Breaker Contact
ColdLoadPickup
0 .. 21600 sec
ColdLoadPickup
1 .. 21600 sec
ColdLoadPickup
1 .. 600 sec; ∞
Phase O/C
ON
OFF
Block relay
Phase O/C
ON
OFF
Phase O/C
I>> instant.
I> instant.
Ip instant.
Inactive
Phase O/C
1A
0.10 .. 35.00 A; ∞
5A
0.50 .. 175.00 A; ∞ 20.00 A
Phase O/C
0.10 .. 35.00 I/InS;
Phase O/C
0.00 .. 60.00 sec; ∞ 0.10 sec
Phase O/C
1A
0.10 .. 35.00 A; ∞
5A
0.50 .. 175.00 A; ∞ 10.00 A
Phase O/C
0.10 .. 35.00 I/InS;
Phase O/C
0.00 .. 60.00 sec; ∞ 0.30 sec
Phase O/C
1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
Phase O/C
0.10 .. 4.00 I/InS
Phase O/C
0.05 .. 3.20 sec; ∞
Phase O/C
0.50 .. 15.00 ; ∞
Phase O/C
Instantaneous
Disk Emulation
Default Setting
Comments
No Current
Start Condition CLP for
O/C Phase
No Current
Start Condition CLP for
O/C 3I0
No Current
Start Condition CLP for
O/C Earth
No Current
Start Condition CLP for
O/C Phase 2
No Current
Start Condition CLP for
O/C Phase 3
No Current
Start Condition CLP for
O/C 3I0 2
No Current
Start Condition CLP for
O/C 3I0 3
No Current
Start Condition CLP for
O/C Earth 2
3600 sec
Circuit Breaker OPEN
Time
3600 sec
Active Time
600 sec
Stop Time
OFF
Phase Time Overcurrent
OFF
InRush Restrained O/C
Phase
I>> instant.
O/C Manual Close Mode
4.00 A
I>> Pickup
4.00 I/InS
I>> Pickup
T I>> Time Delay
2.00 A
I> Pickup
2.00 I/InS
I> Pickup
T I> Time Delay
2.00 A
Ip Pickup
10.00 A
2.00 I/InS
Ip Pickup
0.50 sec
T Ip Time Dial
5.00
D Ip Time Dial
Disk Emulation
TOC Drop-out character-
istic
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016