Addr. Parameter
4312
t(U/f=1.35)
4313
t(U/f=1.40)
4314
T COOL DOWN
4401
THERM. OVERLOAD Therm.Over-
4402
K-FACTOR
4403
TIME CONSTANT
4404
Θ ALARM
4405
I ALARM
4407A Kτ-FACTOR
4408A T EMERGENCY
4409A I MOTOR START
4410
TEMPSENSOR RTD
4411
TEMPSENSOR RTD
4412
TEMP. RISE I
4413
TEMP. RISE I
4420
OIL-DET. RTD
4421
OIL Sensor RTD
4422
HOT SPOT ST. 1
4423
HOT SPOT ST. 1
4424
HOT SPOT ST. 2
4425
HOT SPOT ST. 2
4426
AG. RATE ST. 1
4427
AG. RATE ST. 2
4431
METH. COOLING
4432
Y-WIND.EXPONENT Therm.Over-
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
Function
C
Setting Options
Overexcit.
0 .. 20000 sec
Overexcit.
0 .. 20000 sec
Overexcit.
0 .. 20000 sec
OFF
load2
ON
Block relay
Alarm Only
Therm.Over-
0.10 .. 4.00
load2
Therm.Over-
1.0 .. 999.9 min
load2
Therm.Over-
50 .. 100 %
load2
Therm.Over-
0.10 .. 4.00 I/InS
load2
Therm.Over-
1.0 .. 10.0
load2
Therm.Over-
10 .. 15000 sec
load2
Therm.Over-
0.60 .. 10.00 I/InS;
load2
Therm.Over-
1 .. 6
load2
Therm.Over-
1 .. 12
load2
Therm.Over-
40 .. 200 °C
load2
Therm.Over-
104 .. 392 °F
load2
Therm.Over-
1 .. 6
load2
Therm.Over-
1 .. 12
load2
Therm.Over-
98 .. 140 °C
load2
Therm.Over-
208 .. 284 °F
load2
Therm.Over-
98 .. 140 °C
load2
Therm.Over-
208 .. 284 °F
load2
Therm.Over-
0.200 .. 128.000
load2
Therm.Over-
0.200 .. 128.000
load2
Therm.Over-
ON
load2
OF
OD
1.6 .. 2.0
load2
Functions, Settings, Information
Default Setting
Comments
13 sec
U/f = 1.35 Time Delay
10 sec
U/f = 1.40 Time Delay
3600 sec
Time for cool down
OFF
Thermal Overload Protec-
tion
1.10
K-Factor
100.0 min
Thermal Time Constant
90 %
Thermal Alarm Stage
1.00 I/InS
Current Overload Alarm
Setpoint
1.0
Kt-FACTOR when motor
stops
100 sec
Emergency Time
∞ I/InS
Current Pickup Value of
Motor Starting
1
Temperature sensor
connected to RTD
1
Temperature sensor
connected to RTD
100 °C
Temperature Rise at
Rated Sec. Curr.
212 °F
Temperature Rise at
Rated Sec. Curr.
1
Oil-Detector conected at
RTD
1
Oil sensor connected to
RTD
98 °C
Hot Spot Temperature
Stage 1 Pickup
208 °F
Hot Spot Temperature
Stage 1 Pickup
108 °C
Hot Spot Temperature
Stage 2 Pickup
226 °F
Hot Spot Temperature
Stage 2 Pickup
1.000
Aging Rate STAGE 1
Pickup
2.000
Aging Rate STAGE 2
Pickup
ON
Method of Cooling
1.6
Y-Winding Exponent
F.2 Settings
577