6.2 Initial Setting Mode

To enter Initial setting mode, press and hold the
mode.
To set (or select) each setting item, use the
To register each setting item, press the
Explanation of setting item:
• Upper left: PV Display: Indicates setting characters.
• Lower left: SV Display: Indicates factory default.
• Right side: Indicates the setting item, explanation of its function, and setting range (or selection item).
Setting characters
[1]
Factory default value
Setting item numbers such as [1], [2] are the same as those on Section "14. Key Operation Flowchart"
(p.131).
Characters,
Factory Default
[1]
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Setting item name, function, setting range (or selection item)
Input type
• Selects an input type from thermocouple (10 types), RTD (2 types), Direct current
(2 types) and DC voltage (4 types), and the unit
Setting Item, Function, Setting Range
Input type
• Selects an input type from thermocouple (10 types), RTD (2 types), Direct current
(2 types) and DC voltage (4 type), and the unit
• When changing the input from DC voltage to other inputs, remove the sensor
connected to this controller first, then change the input. If the input is changed
with the sensor connected, the input circuit may break.
• When changing an input type, refer to Section "8.10 Items to be Initialized by
Changing Settings" (p.84).
• Selection item:
K
-200 to 1370
K
-200.0 to 400.0
J
-200 to 1000
R
0 to 1760
S
0 to 1760
B
0 to 1820
E
-200 to 800
T
-200.0 to 400.0
N
-200 to 1300
PL-
0 to 1390
C(W/Re5-26)
Pt100
-200.0 to 850.0
JPt100
-200.0 to 500.0
Pt100
-200 to 850
JPt100
-200 to 500
4 to 20 mA DC -2000 to 10000
0 to 20 mA DC -2000 to 10000
0 to 1 V DC
0 to 5 V DC
1 to 5 V DC
0 to 10 V DC -2000 to 10000
and
keys (in that order) for 3 seconds in RUN
or
key.
key.
0 to 2315
-2000 to 10000
-2000 to 10000
-2000 to 10000
/ .
/ .
K
-328 to 2498
K
-328.0 to 752.0
J
-328 to 1832
R
32 to 3200
S
32 to 3200
B
32 to 3308
E
-328 to 1472
T
-328.0 to 752.0
N
-328 to 2372
PL-
32 to 2534
C(W/Re5-26)
32 to 4199
Pt100
-328.0 to1562.0
JPt100 -328.0 to 932.0
Pt100
-328 to 1562
JPt100 -328 to 932