7.4 Engineering Mode 2

To enter Engineering mode 2, press and hold the
approximately 5 seconds in RUN mode.
Use the
or
To register the set data, use the
Explanation of setting items:
• Upper left: PV Display: Indicates setting characters.
• Lower left: SV Display: Indicates factory default value.
• Right side: Indicates the setting item, explanation of its function and setting range (or selection item).
Setting characters
[90]
Factory default value
Setting item numbers such as [90], [91] are the same as those on Section "14. Key Operation Flowchart"
(p.131).
Characters,
Factory Default
[90]
[91]
[92]
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
key for settings (or selections).
key.
Setting item name, function, setting range (or selection item)
Control method
• Selects usual PID control or 2DOF PID control action.
Setting Item, Function, Setting Range
Control method
• Selects usual PID control or 2DOF PID control action.
DOF: Degree(s) of freedom
PID control
2DOF PID control
Proportional gain 2DOF coefficient (α)
• Sets Proportional gain 2DOF coefficient.
• Setting range: 0.00 to 1.00
Available only when 2DOF PID control is selected in [Control method].
Integral 2DOF coefficient (β)
• Sets Integral 2DOF coefficient.
• Setting range: 0.00 to 10.00
Available only when 2DOF PID control is selected in [Control method].
,
and
keys (in that order) together for