Program control Holding/Not holding
During Program control, progress of current step is suspended, and then Fixed value control is
performed using the SV from the point of suspension.
Program control Holding/Not holding can be selected by communication command bit operation
in Serial communication.
Serial communication can be specified only for the KT4R model.
Advance function
Interrupts current step while Program control is running, and proceeds to the beginning of the next
step.
By pressing the
Pattern end output
If Pattern end output is selected in [Event output EV1/EV2 allocation], pattern end output is turned
ON after Program control is finished, and the SV Display flashes
By pressing the
Standby mode.
Step time unit
Step time unit can be selected: Hours:Minutes, Minutes:Seconds
Factory default value is Hours:Minutes.
Power Restore Action (Program control after power is restored)
If power fails during Program control, selects a status after the power is restored.
Factory default value is 'Stops after power is restored'.
Power Restore Action
Stops after power is
restored.
Continues after power is
restored.
(*)
Suspends after power is
restored.
(*)
(*) Progressing time error when power is restored: 10 minutes
This controller saves internal status every 10 minutes after Program control starts.
Internal status is also saved when step is changed.
When power is restored, the unit starts from the last auto-save point.
Step number
Step time
Auto-save point (●)
Saves internal data every
10 minutes based on
program control start time.
PV start is used. SV and time are
advanced to the remaining time 0:52,
and program control starts.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
key for approx. 1 second during Program control, Advance function initiates.
key for approx. 1 second, pattern end output is turned OFF, and the unit enters
Stops Program control, and returns to Standby (Program control
waiting) mode.
Continues (resumes) Program control.
Suspends (on hold) current program, and performs Fixed value
control using the SV from the point of suspension.
Pressing the
resumes.
1
1:00
If power failure occurs at
remaining time 0:28,
control resumes at ① 0:32.
(Fig. 8.7-3)
Description
key cancels suspension, and Program control
If power failure occurs at remaining time 1:45,
control resumes at ② 1:52.
.
2
2:00