Program start temperature
When Program control starts, it starts from the value set in [Program start temperature].
Factory default value is 0 .
Program control start type
One type can be selected: PV start, PVR start, SV start.
Factory default value is PV start.
Program control
start type
PV start
PVR start
SV start
[SV start]
SV
100
1:00
Program control starts.
SV when Program
control starts
(Fig. 8.7-4)
Repeat function
When Program control is finished, control can be repeated from Step 1.
The user determines the number of repetitions.
Factory default value is 0 (zero).
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
When Program control starts, the SV and step time are advanced to the PV,
then Program control starts.
However, if [Program start temperature] at the time of Program control start is
higher than the PV when PV start is initiated, then Program control will start
from the SV set in [Program start temperature].
In pattern repeating, the SV and step time are advanced to the PV, then the
Program control starts.
Program control starts from the SV which has been set in [Program start
temperature].
Time
Description
[PV/PVR start]
SV
100
25
1:00
0:45
PV start point
Program control starts from the PV
start point (measured value 25
(Fig. 8.7-5)
Time
).