Characters,
Factory Default
[D]
EV1 alarm hysteresis
• Sets EV1 alarm hysteresis.
• Setting range: 0.1 to 1000.0
DC voltage, current inputs: 1 to 10000
Available when any alarm from
limits with standby independent alarm) is selected in [Event output EV1 allocation].
[E]
EV1 alarm delay time
• Sets EV1 alarm action delay time.
When setting time has elapsed after the input enters the alarm output range, the
alarm is activated.
• Setting range: 0 to 10000 seconds
Available when any alarm from
limits with standby independent alarm) is selected in [Event output EV1 allocation].
[F]
EV1 alarm Energized/De-energized
• Selects Energized/De-energized status for EV1 alarm.
(Refer to 'EV1/EV2 Energized/De-energized' on p.40.)
• Selection item:
Available when any alarm from
limits with standby independent alarm) is selected in [Event output EV1 allocation].
[G]
TS1 output step number
• Sets the step number at which Time signal output TS1 will be turned OFF or ON
during Program control.
(Refer to 'Time Signal Output' on p.41.)
• Setting range: 1 to 9
Available only when
[H]
TS1 OFF time
• Sets Time signal output TS1 OFF time.
(Refer to 'Time Signal Output' on p.41.)
• Setting range: 00:00 to 99:59
Available only when
[I]
TS1 ON time
• Sets Time signal output TS1 ON time.
(Refer to 'Time Signal Output' on p.41.)
• Setting range: 00:00 to 99:59
Available only when
(*1)The placement of the decimal point follows the selection.
(*4) Time unit follows the selection from [Step time unit].
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Setting Item, Function, Setting Range
( )
(Alarm output, High limit alarm) to
(Alarm output, High limit alarm) to
Energized
De-energized
(Alarm output, High limit alarm) to
(Time signal output) is selected in [Event output EV1 allocation].
(*4)
(Time signal output) is selected in [Event output EV1 allocation].
(*4)
(Time signal output) is selected in [Event output EV1 allocation].
(*1)
(Alarm output, High/Low
(Alarm output, High/Low
(Alarm output, High/Low

Hide quick links: