Setting Procedure
Power ON
RUN mode
Initial setting mode
Input type
Event output EV1
allocation
EV1 alarm value
SV1
RUN mode
Sub setting mode
AT/Auto-reset
Perform/Cancel
RUN mode
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Setting Detail
Power ON
RUN mode
PV/SV Display
+
(3 sec)
Initial setting mode
Input type [1]
or
: K -200.0 to 400.0
(3 times)
Event output EV1 allocation. [5]
or
: High limit alarm
(Twice)
EV1 alarm value [B]
or
20.0
(Many times)
SV1 [9]
or
200.0
RUN mode
PV/SV Display (Fixed value control)
+
Sub setting mode
AT/ Auto-reset Perform/Cancel [37]
or
Perform AT.
The AT indicator flashes while AT is performing.
The AT indicator goes off after AT is completed.
PV/SV Display (Fixed value control)