5 UTILITY PACKAGE (GX Configurator-AD)

5 UTILITY PACKAGE (GX Configurator-AD)

5.1 Utility Package Functions

Table 5.1 Utility package (GX Configurator-AD) function list
Item
1
Initial setting
5
Automatic refresh
1
setting
Monitor/Test
FB conversion
5 - 1
Table 5.1 shows an overview of the utility package functions.
(1) Sets the following items that require initial setting.
• A/D conversion enable/disable setting
• Averaging process specification
• Average time/Average number of times/Move average/
Time constant settings
• A/D conversion starting time setting (Q62AD-DGH)
• Warning output settings (Process alarm setting)
• Process alarm upper upper limit value/upper lower limit value/
lower upper limit value/lower lower limit value
• Warning output settings (Rate alarm setting)
• Rate alarm upper limit value/lower limit value
• Rate alarm warning detection period
• Input signal error detection setting
• Input signal error detection setting value
(2) The data for which initial setting has been completed is registered in
the parameters for the PLC CPU, and automatically written to the
A/D converter module when the PLC CPU changes to the RUN
status.
(1) Sets automatic refresh for the A/D converter module buffer memory.
(2) The buffer memory that was set for automatic refresh is
automatically read and written to the specified device when the
END command for the PLC CPU is executed.
(1) Monitor/Test
The buffer memory and I/O signals for the A/D converter modules
are monitored and tested.
(2) Operating condition setting
Changes the A/D operating status during operation.
(3) Offset/gain setting
When setting the offset/gain to a value selected by the user (when
the analog output range setting is user range setting), the offset and
gain can be easily set while viewing the screen.
(4) Pass data
The pass data (industrial shipment settings offset/gain values, user
range settings offset/gain values) can be monitored and set.
Generates FB automatically from the intelligent function module
parameter (initial setting/auto refresh setting).
POINT
1 If initial setting and automatic refresh setting are performed, the intelligent
function module parameters require a maximum of 76 bytes per module.
Description
MELSEC-Q
Reference section
Section 5.4
Section 5.5
Section 5.6
Section 5.7
5 - 1