Mitsubishi Q64AD-GH User Manual page 43

Melsec-q series, programmable logic controller, channel isolated high resolution analog-digital converter module with signal conditioning function
Hide thumbs Also See for Q64AD-GH:
Table of Contents

Advertisement

3 SPECIFICATIONS
Signal direction CPU Module
Device No. (Input)
X0
Module ready
X1
X2
X3
X4
X5
X6
X7
X8
Warning output signal
X9
Operating condition setting completed flag
XA
Offset/gain setting mode flag
XB
Channel change completed flag
Input signal error detection signal
XC
Offset/gain change completed flag
Maximum value/minimum value reset
XD
completed flag
XE
A/D conversion completed flag
XF
Error flag
3 - 20
Table 3.5 List of I/O signal (Q62AD-DGH)
Q62AD-DGH
Signal name
1
Use prohibited
POINT
1 These signals cannot be used by the user since they are for system use only.
If these are turned ON/OFF by the sequence program, the functioning of the
A/D converter module cannot be guaranteed.
Signal direction CPU Module
Device No. (Output)
Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7
Y8
Y9
Operating condition setting request
YA
User range writing request
YB
Channel change request
YC
Offset/gain change request
Maximum value/minimum value reset
YD
request
Use prohibited
YE
YF
Error clear request
MELSEC-Q
Q62AD-DGH
Signal name
1
Use prohibited
1
3 - 20

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Sw2d5c-qadu-eQ62ad-dghGx configurator-ad

Table of Contents